Download User Manual - ProSoft Technology
Transcript
Page 28 AN-X-MOD (Master) November 2011 All items are of the form offset [optional], ItemKeyword If you create the ControlLogix configuration automatically when you autoconfigure the S908 network, these items are mapped by default to ClxSlot 15. TIP If you map the diagnostic data to a separate connection, use a long RPI to reduce the Ethernet traffic, since the diagnostics do not need to be updated as frequently as I/O data. Diagnostic Counters The AN-X-MOD (Master) maintains the following diagnostic counters. Counter Offset Description TxCount 0 Transmitted network frames RxGood 1 Received frames with good status RxPrtcl 2 Received frames with a protocol error RxNoise 3 Received frames with a noise error RxTout 4 Receive timeout. Scanner sent a message to a drop but did not receive a reply within the timeout period RxCrc 5 Received frames with a CRC error RxOvr 6 Received frames too long RxAbort 7 Received frames with an abort error RxShort 8 Received frames too short RxErrMask 9 Error mask for protocol errors To map the diagnostic counters, include a line with the keyword DiagCtrs in the input section of a connection. This maps all ten diagnostic counters; they cannot be mapped individually. Examples: , DiagCtrs 10, DiagCtrs ; offset 10