Download AL2 Programming Manual
Transcript
α2 6.8 Function Blocks 6 Simple Application Controllers One Shot Block The function block gives a single Output pulse for a controlled duration of time. If the Set Time is 0.0 seconds, the block will function like the Pulse block. The Reset Input returns the Output to the OFF condition and will override the Input pin. Table 6.8: One Shot Function Block Function Set Item Description I Input pin for one shot operation C Clear input pin resets the state of the output regardless of the input Time units: 10ms, 100ms or 1s (*Note) FB I C 000 P O The One Shot time T and t can be set using the chosen time units. A Time or Input priority can be set. The following items are applicable for the one shot function block: OS 1) A period of 0s to 32767s for a single pulse output can be set. Output 2) The output is turned ON during the single shot time duration as and when the input pin receives a signal. 3) The output is cleared as and when the clear pin receives a signal. 4) The following items are available for other function blocks: a) One Shot b) Current One Shot Note: The set time cannot be less than one scan time for the controller; otherwise, the One Shot Function Block will not perform its assigned task for the time specified. Users can monitor the scan time from the α2 Series Controller. Scan time is dependent on the user-program; therefore, caution is needed as and when time units are selected. One Shot Operation 1 ) Time Priority Input pin I Input pin C Output ON OFF set time set time 2 ) Input priority Input pin I Input pin C Output set time 6 - 16