Error
code
Error name
Error details and cause
1993H
Software stroke limit +
• The feed current value exceeded the stroke limit range
at start.
• The feed current value exceeded the stroke limit range
when controlling. Only the axes which exceeded the
stroke limit range are stored in case of the circular
interpolation/helical interpolation. All of the interpolations
are stored in case of the linear interpolation.
• Set within the stroke range by the JOG operation. Or set
within the stroke range by the home position return or
current value change.
• Correct the stroke limit range or movement amount
setting so that positioning control is within the range of
the stroke limit.
1995H
Software stroke limit -
• The feed current value is lower than the stroke lower
limit value at start.
• The feed current value is lower than the stroke lower
limit value when controlling. Only the axes which
exceeded the stroke limit range are stored in case of the
circular interpolation/helical interpolation. All of the
interpolations are stored in case of the linear
interpolation.
• Set within the stroke range by the JOG operation. Or set
within the stroke range by the home position return or
current value change.
• Correct the stroke limit range or movement amount
setting so that positioning control is within the range of
the stroke limit.
1997H
Current value change
outside range
The current value was changed outside the range of 0 to
35999999 (10-5 [degree]) for the degree axis.
19A1H
PLC ready OFF start
The "[Rq.1120] PLC ready flag" or the "PCPU preparation
completion flag" is OFF.
19A4H
ABS direction setting
error during degree
When software stroke limit is invalid, the value outside the
range has been set to "ABS direction setting device during
degree".
19A6H
Start error during home
position return
incomplete
The "[St.1069] Home position return request" is ON if the
"Servo program not executed" is selected in the operation
setting when the home position is not completed.
19DFH
Stop function valid
setting error for backing
side
Enable the stop function valid setting to backing side of
servo parameter (PT12: TOP1 pressure control function
selection 1).
19E0H
Pressure control exceed
last address error
19E1H
Pressure control start
error
19E2H
Command speed
acceleration/deceleration
time outside range
• The command speed acceleration time of the speedtorque control data is outside the range 0 to
8388608 [ms].
• The command speed deceleration time of the speedtorque control data is outside the range 0 to
8388608 [ms].
• Set the command speed acceleration time of the speedtorque control data within the range 0 to 8388608 [ms].
• Set the command speed deceleration time of the speedtorque control data within the range 0 to 8388608 [ms].
19E3H
Command torque time
constant outside range
• The command torque time constant (positive direction)
of the speed-torque control data is outside the range of 0
to 8388608 [ms].
• The command torque time constant (negative direction)
of the speed-torque control data is outside the range of 0
to 8388608 [ms].
• Set the command torque time constant (positive
direction) of the speed-torque control data within the
range of 0 to 8388608 [ms].
• Set the command torque time constant (negative
direction) of the speed-torque control data within the
range of 0 to 8388608 [ms].
19E6H
Target position change
request prohibited
acceleration/deceleration
method
The target position change request (CHGP) is executed to
the program where the following acceleration/deceleration
system is set.
• FIN acceleration/deceleration
• Advanced S-curve acceleration/deceleration
19E7H
Unsupported stopper
control
Switching to the stopper control was requested to the
servo amplifier which unsupported to the stopper control.
Use the available stopper control for servo amplifier.
19E8H
Stroke limit invalid axis
circular/helical
interpolation execution
error
The circular interpolation or helical interpolation was
started in the invalid axis of stroke limit.
Make the stroke limit valid for the control unit degree axis
starts the circular interpolation or helical interpolation.
• The difference between last address and home position
exceed motor encoder pulse unit  (2-31 pulse to motor
encoder for 10 rev.).
• The difference between last address and actual current
value exceed motor encoder pulse unit (2-31pulse).
Necessary setting value for pressure control starting is
outside the range.
Corrective action
Operate within the range of 0 to 35999999 (10-5[degree]).
• Set the Motion CPU to RUN.
• Turn the "[Rq.1120] PLC ready flag" on.
Set the ABS direction setting device during degree within
the range.
• After the home position return is accomplished, execute
the servo program.
• For systems that allow the execution of the servo
program even if a "[St.1069] Home position return
request" is ON, set "Operational setting for home
position return incomplete" of the home position return
data setting to "Execute servo program".
Disable the stop function valid setting for backing side.
Correct the value of last address to make it within the
setting range of limit value.
Correct the setting value.
• Do not execute the target position change to the
program where the FIN acceleration/deceleration or the
advanced S-curve acceleration/deceleration is set.
• Set the acceleration/deceleration system of the
parameter block or the servo program to the trapezoid/
S-curve acceleration/deceleration.
APPENDICES APPENDIX
Appendix 1 Error Codes
259