Download caution - Schneider Electric
Transcript
Equipment Control MotAct - Description General The MotAct block is implemented as listed in the following table: Software Implemented as Unity Pro DFB MotAct Vijeo Citect Genie MotAct UAG SCoD MotAct Function Description The MotAct block is used to control electrical actuators with defined positions used for driving valves, gates, dampers, and so on. This block supports 3 modes of operation: z Auto mode z Manual mode z Local mode By default, the motor will be in Auto mode. The motor is forced to Auto or Local mode if the mode selection input pin (AutoSel or LOC) is HIGH. The Local pin always has highest priority. When the Local mode is selected, the block functions in Local mode irrespective of other mode selections. If the mode selection input pin (AutoSel or LOC) is LOW, operator changes mode of the motor from the popup of motor block. When the motor is under maintenance, the Out of Service mode can be activated from the popup. Auto Mode Operation A wake-up command (Wake) is given by the GrpCtrl block to wake-up the motor from sleep. A start-up pulse command to achieve position is given either from the GrpCtrl or GrpStrtMgt or RouteMgt or previous device in the group. If Direction is 0, this sets the output OP1 as HIGH and actuator starts to selected position1. If Direction is 1, this sets the output OP2 as HIGH and actuator starts to selected position2. After the start command (OP1) or (OP2) is issued to the actuator within the specified position feedback delay, the position feedback has to be obtained. If the position feedback is not obtained, the actuator is tripped, and an alarm is generated. If the position feedback is obtained, the actuator stops. EIO0000000886 07/2011 261