Equipment Control
The stop command (Stop) is issued and output (OP) is set LOW when the run
feedback (FbRun) is set LOW. Run output (Run) is set LOW and command
(SeqStop) is given to the next device to stop.
The quick stop command (QStop) is issued and output (OP) is set LOW and
command (SeqStop) is given to the next device to stop.
Interlock Types
There are 4 types of interlocks. The result of individual interlock condition blocks is
connected to these interlock pins:
Interlock Name
Parameter
Description
Starting Interlock
StartILck
These interlocks are valid before motor start-up
only.
Safety Interlock
SftyILck
All the safety conditions are taken into
consideration. This input is active in all the modes.
Sequential Interlock
SeqILck
All the sequential conditions are taken into
consideration. This input is active only in Auto
mode.
Process Interlock
ProcILck
All the process conditions are taken into
consideration. This input is active in Auto and
Manual mode.
The status of the interlock is displayed in the popup. Detailed description of the
interlocks is displayed in the Interlock tab of the popup.
The availability (Avail) of the motor is continuously monitored. If motor is started
and it is not operational, the motor is tripped, and an alarm is generated. The
overload feedback (OverLoad) of the motor is continuously monitored. If motor is
started and it is not operational, the motor is tripped, and an alarm is generated.
The alert and trip are indicated in the SCADA. The number of active alarms is shown
in the popup of the motor. The details of the active alarms are shown in the Alarm
tab of the popup. Based on configured conditions, the alarms for this block can be
inhibited by connecting the logic to the input pin AlmInh. The input pin AlmRst that
is connected from GrpCtrl block or the operator from popup can reset the trip
alarms.