Cement Process
Parameter
Type
Description
Details
ExtTotalSP
REAL
External total set
point
z Applicable in External and Auto
External ratio for
set points x
(x: 1...6)
Applicable in External modes only.
Set poins are generated based on the
external ratio inputs.
Output 1...6 x
(x: 1...6) enable
z OP1Enx (x: 1...6) = 1: Output x is
ExtRatiox
(x: 1...6)
REAL
OP1Enx (x: 1...6) BOOL
modes only if the
ExtTotalSPEnable is selected
from popup.
z In External mode, it is divided into
individual set points based on the
ratio input pins. In Auto mode, it is
divided into individual set points
based on the ratio entered by
operator from HMI.
z Must be connected from other
blocks (For example, Systems
(Expert control systems) or PID
Controller).
controlled by the block.
z OP1Enx (x:1...6) = 0: Output x is
not controlled by the block.
CAUTION
UNINTENDED MACHINE OR PROCESS BEHAVIOR
Be sure of the state of security of your machine or process environment.
The AlmInh parameter to inhibit alarms muste be used very carefully.
Failure to follow these instructions can result in injury or equipment damage.
The following table describes the input parameter of the MultiFuelCtrl block:
Parameter
Type
Description
Details
AlmInh
BOOL
Alarm inhibition
z AlmInh = 1: Except for safety
alarms, all the other alarms are
inhibited. No alarms are
generated by the block.
z AlmInh = 0: Alarms are not
inhibited.
EIO0000000886 07/2011