Download AssetView Users Manual
Transcript
AssetView 3.1 - User’s Manual Diagnosis Shows the status of the continuous diagnostic for the device, including the condition of the function block, the electronic module and the sensor. BLOCK CONFIGURATION ERROR LINK CONFIGURATION SIMULATION ACTIVE LOCAL OVERRIDE POWER UP INPUT FAILURE OUTPUT FAILURE MEMORY FAILURE LOST STATIC DATA LOST NV DATA OUT OF SERVICE DEVICE NEEDS MAINTENANCE NOW GENERAL ERROR CALIBRATION ERROR CONFIGURATION ERROR ELECTRONICS FAILURE MECHANICAL FAILURE I/O FAILURE DATA INTEGRITY ERROR SOFTWARE ERROR ALGORITHM ERROR indicates that there is an error related to the XD_SCALE parameter in the AI function block. indicates the error status of a link. indicates that the device is on simulation mode. indicates that the device is being operated manually. indicates that the device has finalized a power up procedure. indicates failure in the input signal. indicates failure in the output signal. indicates an electronic failure according to the internal checkup process, such as an incorrect checksum detected in the main memory. indicates that the device lost data from the flash or the EEPROM memory. indicates that the device lost data from the RAM memory. indicates that the function block is out of service. the internal diagnostic according to the user configuration or device internal checkup has detected that the device needs maintenance. This diagnostic is related to the sensor of the calibration. a general error related to the device has been detected. indicates that an error occurred during the calibration of the device, or that a calibration error has been detected while operating the device. an error occurred during the configuration of the device or a configuration error has been detected while operating of the device. an electronic component has failed. E a mechanical component has failed. Indicates that an I/O failure has occurred. indicates that data stored in the system may be no longer valid, for example, because the checksum of the data in the RAM memory has failed when compared to the data in the non-volatile memory. the software has detected an error that could have been caused by an improper interruption of a service routine, an arithmetic overflow, a watchdog timer, etc. the algorithm used in the transducer block generated an error. This could be due to an overflow, data reasonableness failure, etc. Magnetrol PulsarTM Calibration Page This page displays configuration data used in the calibration procedures. L.4