AssetView 3.1 - User’s Manual
Diagnosis
Shows the status of the continuous diagnostic for the device, including the condition of the function
block, the electronic module and the sensor.
BLOCK CONFIGURATION
ERROR
LINK CONFIGURATION
SIMULATION ACTIVE
LOCAL OVERRIDE
POWER UP
INPUT FAILURE
OUTPUT FAILURE
MEMORY FAILURE
LOST STATIC DATA
LOST NV DATA
OUT OF SERVICE
DEVICE NEEDS MAINTENANCE
NOW
GENERAL ERROR
CALIBRATION ERROR
CONFIGURATION ERROR
ELECTRONICS FAILURE
MECHANICAL FAILURE
I/O FAILURE
DATA INTEGRITY ERROR
SOFTWARE ERROR
ALGORITHM ERROR
indicates that there is an error related to the XD_SCALE
parameter in the AI function block.
indicates the error status of a link.
indicates that the device is on simulation mode.
indicates that the device is being operated manually.
indicates that the device has finalized a power up procedure.
indicates failure in the input signal.
indicates failure in the output signal.
indicates an electronic failure according to the internal
checkup process, such as an incorrect checksum detected in
the main memory.
indicates that the device lost data from the flash or the
EEPROM memory.
indicates that the device lost data from the RAM memory.
indicates that the function block is out of service.
the internal diagnostic according to the user configuration or
device internal checkup has detected that the device needs
maintenance. This diagnostic is related to the sensor of the
calibration.
a general error related to the device has been detected.
indicates that an error occurred during the calibration of the
device, or that a calibration error has been detected while
operating the device.
an error occurred during the configuration of the device or a
configuration error has been detected while operating of the
device.
an electronic component has failed.
E a mechanical component has failed.
Indicates that an I/O failure has occurred.
indicates that data stored in the system may be no longer
valid, for example, because the checksum of the data in the
RAM memory has failed when compared to the data in the
non-volatile memory.
the software has detected an error that could have been
caused by an improper interruption of a service routine, an
arithmetic overflow, a watchdog timer, etc.
the algorithm used in the transducer block generated an
error. This could be due to an overflow, data reasonableness
failure, etc.
Magnetrol PulsarTM Calibration Page
This page displays configuration data used in the calibration procedures.