Download User Manual - Rockwell Automation
Transcript
Options Programming Parameters 6-3 The following table provides the option-specific parameters that are provided with each control option. These parameters are in addition to those already discussed in the Basic Set Up and Metering groups. Diagrams supporting the options described below are shown later in this chapter. Option Parameter Range Standard Soft Stop SMC Option This parameter identifies the type of control present and is not user programmable. Standard Soft Stop Time Allows the user to set the time period for the soft stopping function. 0…120 s SMC Option This parameter identifies the type of control present and is not user programmable. Standard Slow Speed Select Allows the user to program the slow speed that best fits the application. Preset Slow Speed Low: 7% – Forward, 10% – Reverse 15% – Forward, 20% – Reverse High: Slow Speed Direction This parameter programs the slow speed motor rotational direction. Forward, Reverse Slow Accel Current Allows the user to program the required current to accelerate the motor to slow speed operation. 0…450% of full load current Slow Running Current Allows the user to program the required current to operate the motor at the slow speed setting. 0-450% of full load current SMC Option This parameter identifies the type of control present and is not user programmable. Pump Control Pump Stop Time Allows the user to set the time period for the pump stopping function. 0…120 s Starting Mode Allows the user to program the SMC-Flex controller for the type of starting that best fits the application. Pump Start, Soft Start, Current Limit Start, Full Voltage Pump Control Pump Control 1560E-UM050B-EN-P - June 2013