CATALYST
25. Select #2 H-Factor.
26. Flush the system by the same procedure in step 17
27. Press 0 to exit to the main menu.
28. Enable the system by holding down the [ENT] key and pressing [YES]
Time Based Calibration
Due to certain circumstances, it may be beneficial to calibrate the chemicals
based on time rather than flow meter input.
To calibrate the chemicals without the flow meter, do the following:
Follow the normal calibration procedure. At step 9 select #2 for Time
Based Calibration.
Press YES to dispense the chemical as described in step 11. The
controller will display the time on the screen in tenths of a second.
Once the product has been dispensed, press enter to accept the counts
and then enter in the received amount. The controller will automatically
save the calibration as the Initial calibration.
The Catalyst will now dispense that particular chemical without reference
from the flow meter.
There is no need to change the programming on the machines or
interfaces, the Catalyst will still dispense the chemical in the desired units.
On time based delivery, the controller will open the chemical valve and
turn on the pump for a specified time. If there is no flow or lack of product,
the Catalyst will not alarm.
Calibration Errors0 cannot be entered in for a Calibration.
If No counts or low counts (<1 per second) are detected, the Catalyst will
alarm with a Minimum Frequency Error. If this occurs, press No to exit
and check the flow rate as well as the response from the meter.
Checking the Calibration
WARNING: DO NOT USE THE CALIBRATION ROUTINE TO
CHECK CALIBRATION ACCURACY OR THE CALIBRATION WILL
BE ALTERED. INSTEAD, PROGRAM A CALIBRATION TEST
FORMULA.
42