Download Foreword
Transcript
Chapter 5 Function parameter Code Parameter name Factory default Setting range Change Number of automatic fault reset: when the inverter selects automatic fault reset, it is used to set the number of times of automatic fault reset. When the times of the inverter continuous reset exceed this value, the inverter fault standby, the manual intervention is required. Automatic fault reset interval setting: choose interval between fault occurrence and automatic reset. Descending frequency F8.09 point of momentary power failure Frequency fall rate of F8.10 momentary power failure 70.0 to 110.0% (standard bus voltage) 80.0% ☆ 0.00Hz/s to F0.08 (maximum output frequency) 0.00Hz/s ☆ 5-2-11.F9 Group - Communication parameter group Code F9.00 Parameter name Communication baud rate setting Factory Change default Setting range 1200bps 0 2400bps 1 4800bps 2 9600bps 3 19200bps 4 38400bps 5 3 ☆ This parameter is used to set the data transfer rate between the host computer and the inverter. Note: the baud rate must be set to the same for the host computer and the inverter, otherwise communication can not be achieved. The larger baud rate, the faster communication speed. F9.01 Data bits parity settings 0: no parity (N, 8, 1) for RTU 1: even parity (E, 8, 1) for RTU 2: odd parity (O, 8, 1) for RTU 3: no parity (N, 8, 2) for RTU 4: even parity (E, 8, 2) for RTU 5: odd parity (O, 8, 2) for RTU 6: no parity (N, 7, 1) for ASCII 7: even parity (E, 7, 1) for ASCII 8: odd parity (O, 7, 1) for ASCII 9: no parity (N, 7, 2) for ASCII 73 1 ☆