Download ControlLogix Drive Module
Transcript
1756-DMD30 Specific Information B-55 No. Name Description Values 183 PI Command Set bits to configure the process control regulator -enable or disable the regulator, enable or disable the time function generator and limit generator. Default: 0000 0000 0000 0000 0000 0000 0000 0000 Options: Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 16 Bit 17 Bit 18 Bit 19 Bit 20 Bit 21 Bit 22 Bit 23 Bit 24 Bit 25 Bit 26 Bit 27 Bit 28 Bit 29 Bit 30 Bit 31 File: Group: Process Control Process Config Enable Time Lim En Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 184 PI Lpass Filt BW Sets the bandwidth of a single pole filter applied to the error input of the Process Control regulator. The input to the filter is the difference between parameter 181 [PI Reference] and parameter 182 [PI Feedback]. The output of this filter is used as the input to the process control regulator. Units: Default: Min: Max: Type: File: Group: R/S 0 0 500 Linkable, Read-Write, Floating Point Process Control Regulator 185 PI Preload Presets the integrator. Units: Default: Min: Max: Type: File: Group: P.U. 0 -8 8 Linkable, Read-Write, Floating Point Process Control Regulator Publication 1756-UM522B-EN-P - February 2003