Download Wireless Sensing Technology
Transcript
11.15 ANALOG OUTPUT Analog Output Wiring (Voltage PWM) 0 AO1 AO2 External Device Voltage Input 0-10V (PWM) R V 0 Analog outputs specifications The Analog output signal is derived from a PWM signal. This signal must still be filtered externally before it can be considered a pure voltage output Analog Voltage Output: 0 to 10VDC +/- 0.6% MAX External power supply: use only 12VDC supply Minimum External Load: 10K ZigSense User Manual Rev.C - 69 -