399092.book Page 8 Friday, November 21, 2003 3:57 PM Section 1—Hardware Setup Connection to the Bus Bulletin No. VVDED399092US 07/00 When connecting the ATV28 controller to the RS-485 bus: • Make connections only to pins 3, 4, 6, and 7 of the 9-pin Sub-D cable receptacle. • Use a shielded cable with two pairs of twisted conductor. Cables are available from Square D in lengths of: — 328 ft (100 m) TSX-CSA100 — 658 ft (200 m) TSX-CSA200 — 1640 ft (500 m) TSX-CSA500 • Connect the communication reference potentials to each other. • Do not exceed maximum line length of 3280 ft (1000 m). • Do not exceed maximum tap-off length of 65 ft (20 m). • Do not connect more than 18 nodes on one bus. • Terminate both ends of the bus with a 120 Ω resistor in series with a 0.001 µf capacitor as shown in Figure 3. E N G L I S H 120 Ω D(A) 0.001 µF D(B) Figure 3: 8 Zt Line Terminator © 2000 Schneider Electric All Rights Reserved