Overcurrent element i) Low - set Low-set setting I > 0.10 ~ 2.50 x I n step 0.01 Time multiplier 0.02 ~ 1.0 step 0.01 Definite time setting 0 ~ 10.0 s step 0.01 10.0 ~ 100 s step 0.1 100 ~ 300 s step 1 Reset ratio 95% typical IDMT curve and accuracy class (IEC255 -3) Normal inverse (E5) Very inverse (E5) Extremely inverse (E7.5) Long-time inverse (E5) ii) High -set High-set setting I >> 0.1 to 10 I n step 0.05 10 to 40 In step 0.1 Definite time setting 0 ~ 10.0 s step 0.01 10.0 ~ 100 s step 0.1 100 ~ 300 s step 1 Earth fault element i) Low-set Low-set setting Io > 0.05 ~ 1.0 x I n step 0.01 Time multiplier 0.02 ~ 1.0 step 0.01 0 ~ 10.0 s step 0.01 10.0 ~ 100 s step 0.1 100 ~ 300 s step 1 Definite time setting Reset ratio 95% typical IDMT curve and accuracy class (IEC255 -3) Normal inverse (E5) Very inverse (E5) Extremely inverse (E7.5) Long -time inverse (E5) ii) High -set High-set setting I >> Definite time setting 0.05 ~ 10.0 x I n step 0.05 0 ~ 10.0 s step 0.01 10.0 ~ 100 s step 0.1 100 ~ 300 s step 1 50