Download frames 1-3
Transcript
9-8 Technical Specifications Supply Harmonic Analysis (230V filtered) Assumptions: (Short circuit fault to Neutral) 5kA short circuit supply capability at 230V 1φ, equivalent to 146µH supply impedance 7.5kA short circuit supply capability at 230V 3φ, equivalent to 56µH supply impedance 10kA short circuit supply capability at 400V 3φ, equivalent to 73µH supply impedance h= 2 THD(V) x 100 = ∑ Q h2 h = 40 Q % 1n where Q1n is the rated rms value of the fundamental voltage of the supply transformer. The results conform to stage 1 and stage 2 of the Engineering Recommendation G.5/4 February 2001, Classification ‘C’: Limits for Harmonics in the UK Electricity Industry. Drive Type Motor Power (kW) Fundamental Voltage (V) Typical Motor Efficiency % Harmonic No. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 40 Total RMS Current (A) THD (V) % 0.25 230 85 0.37 230 85 0.55 230 85 0.75 230 85 650V 1.1 230 85 1.5 230 85 2.2 230 85 3.0 230 85 4.0 230 85 TBA TBA TBA RMS Current (A) 7.4 7.5 7.8 8.2 9.0 10.3 1.4 0.2 1.9 2.2 2.9 3.9 2.9 0.4 4.4 4.6 4.8 5.2 1.1 0.5 1.9 2.0 2.3 2.5 0.2 0.2 0.2 0.3 0.4 0.4 0.1 0.1 0.2 0.2 0.2 0.3 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.1 0.1 0.1 0.1 0.0 0.1 0.0 0.0 0.0 0.1 0.0 0.0 0.0 0.0 0.0 0.1 0.0 0.0 0.0 0.0 0.0 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8.2 0.3559 7.5 0.0972 9.3 0.5426 9.9 0.5733 10.9 0.6277 12.5 0.7055 650V AC Drive