Chapter 6 Description of Function Parameters
Tips
Generally, ACI port is used as current input port. If necessary,
it can be used as voltage input port, which can be selected
through a jumper on the control panel. Their correlation can be
converted as 20mA=10.0V.
F5.04 Pulse input lower limit frequency Setting range: 0.0~upper limit
frequency
Default value: 0.0KHz
Chapter 6 Description of Function Parameters
F5.08 Analog input signal delay period Setting range: 0.1~50.0s Default value: 0.5s
This parameter is used to regulate the delay period of analog input signal.
F5.09 Multi-function analog output AFM Setting range: 0~7 Default value: 0
F5.10 Multi-function digit output DFM Setting range: 0~7 Default value: 2
Fig.6-11 Relation Curve of Input Quantity against Setting Frequency
This function is used to select output signal at the analog ou tput port AFM
and digital output port DFM.
Output frequency
AFm:(0~AFM Upper limit value )=(0.00~Upper limit frequency)
DFm:(0~DFM Upper limit value )=(0.00~Upper limit frequency)
1:Setting frequency
AFm:(0~AFM Upper limit value )=(0.00~Setting frequency)
DFm:(0~DFM Upper limit value )=(0.00~Setting frequency)
2: Output current
AFm:(0~AFM Upper limit value )=(0.00~2 times for rated current)
DFm:(0~DFM Upper limit value )=(0.00~2 times for rated current)
3:Motor rotating speed
AFm:( 0~AFM Upper limit value )=(0.00~2 Motor synchronous rotating
speed)
DFm:( 0~DFM Upper limit value )=(0.00~2 Motor synchronous rotating
speed)
4:Output voltage
AFm:(0~AFM Upper limit value )=(0.00~Maximum/Rated output
voltage)
DFm:(0~DFM Upper limit value )=(0.00~Maximum/Rated output
voltage)
5:Bus bar voltage
AFm:(0~AFM Upper limit value )=(0.00~800V)
DFm:(0~DFM Upper limit value )=(0.00~800V)
6:PID given value
AFm:(0~AFM Upper limit value )=(0.00~10.00V)
DFm:(0~DFM Upper limit value )=(0.00~10.00V)
7:PID feedback value
AFm:(0~AFM Upper limit value )=(0.00~10.00V)
DFm:(0~DFM Upper limit value )=(0.00~10.00V)
-92-
-93-
F5.05 Pulse input upper limit frequency Setting range: Lower limit
frequency~20.0KHz
Default value: 10.0KHz
F5.04 and F5.05 are applied to set the maximum and minimum values
for external input pulse, which should be set in accordance with actual
situation of input signal.
F5.06 Minimal input corresponding frequency Setting range: 0.00~upper
limit frequency
Default value: 0.00Hz
F5.07 Maximum input corresponding frequency Setting range: 0.00~upper
limit frequency
Default value: 50.00Hz
This set of parameters is used to set the correlation between external
analog input quantity and the set frequency. The relationship between set
frequency and frequency setting signal after treatment of f iltering and
gain is shown in Fig.6-11. These two kinds of signals can realize the
characteristics of direct action and reaction separately. fmax an d fmin
in this figure refer to the frequency corresponding to the upper limit of
input and the lower limit of input respectively.
Frequency