Download User`s Manual
Transcript
Chapter 1 Safety Instructions Chapter 1 Safety Instructions Inverter G Proper grounding method Inverter G Inverter G Grounding bus bar (Connect to the ground at the shared point) CAUTION Figure 1-1 FORBIDDEN DO NOT connect control terminals (except terminals mar ked "TA", "TB" and "TC") to AC 220V power supply, which may cause damage to the inverter. DO NOT connect AC power supply to the output terminals marked "U", "V" and "W". Otherwise, it may cause damage to the inverter, as shown in the Figure 1-2. It is not suitable to install an electromagnetic contactor in the side of output power supply, because the operation of open and close to the contactor when the motor is running may cause damage to the inverter arising from over-voltage produced during this process. But it is still necessary to install a contactor if one of the following three points occurs: 1. The system of frequency converting governor used to control energy-saving usually works at a rated rotation speed. To run the governor economically, there is a must to remove the inverter. 2. The inverter participates in some import procedure and cannot stop operating for a long period of time. To realize free shift in various control systems and improve the reliability of these systems, there is a must to install a contactor. 3. When an inverter controls several motors, there is a must to install a contactor. Caution: DO NOT operate the contactor if there is output of the inverter. 1.5 Cautions for Operation FORBIDDEN Three-phase AC Power Supply R S T U INVERTER V W Figure 1-2 COMPULSORY DO install a no-fuse circuit breaker or leakage protective circuit breaker in the side of inverter input power supply to prevent expanding of accident due to an inverter problem. -4- HAZARD Do not operate electrical equipment with wet hands. An inverter stored for more than half a year should be given power up test before use so that the main circuit filter capacitor could be recovered. When the inverter is in the state of powerup, it is necessary to raise the voltage gradually to the rated value with a voltage regulator. Generally, the charging time should be controlled within 2 hours. Otherwise, there is the danger of electric shock or exposure. Do not touch the inner side of the inverter while the po wer is ON, nor put any foreign matter, i.e., rod or other matter inside the inverter. Otherwise, it may result in serious damage to the equipment or electric shock. Do not open the front cover while the inverter is powered ON. Otherwise, there is the danger of electric shock. Be careful to select the Restart Mode. Otherwise, there is the danger of personnel death. -5-