Download [1.7 APPLICATION FUNCT.] (FUn
Transcript
[1.3 SETTINGS] (SEt-) Code Name/Description M [Auto DC inj. level 1] SdC1 g Adjustment range Factory setting 0 to 1.2 In (1) 0.7 In (1) Level of standstill DC injection current. This parameter can be accessed if [Auto DC injection] (AdC) page 164 is not [No] (nO) This parameter is forced to 0 if [Motor control type] (Ctt) page 72 = [Sync. mot.] (SYn) or [Sync.CL] (FSY). CAUTION Check that the motor will withstand this current without overheating. Failure to follow this instruction can result in equipment damage. 0.1 to 30 s M [Auto DC inj. time 1] tdCI 0.5 s Standstill injection time. This parameter can be accessed if [Auto DC injection] (AdC) page 164 is not [No] (nO) If [Motor control type] (Ctt) page 72 = [FVC] (FUC) or [Sync. mot.] (SYn) or [Sync.CL] (FSY) this time corresponds to the zero speed maintenance time. g M [Auto DC inj. level 2] SdC2 g 0 to 1.2 In (1) 0.5 In (1) 2nd level of standstill DC injection current. This parameter can be accessed if [Auto DC injection] (AdC) page 164 is not [No] (nO) This parameter is forced to 0 if [Motor control type] (Ctt) page 72 = [Sync. mot.] (SYn) or [Sync.CL] (FSY). CAUTION Check that the motor will withstand this current without overheating. Failure to follow this instruction can result in equipment damage. YES SdC2 Operation x I SdC1 SdC2 Ct 0 I SdC1 tdC1 t tdC1 + tdC2 SdC2 Ct 0s 2nd standstill injection time. This parameter can be accessed if [Auto DC injection] (AdC) page 164 = [Yes] (YES) g AdC 0 to 30 s M [Auto DC inj. time 2] tdC2 =0 I SdC1 tdC1 Note: When [Motor control type] (Ctt) page 72 = [FVC] (FUC) or [Sync.CL] (FSY): [Auto DC inj. level 1] (SdC1), [Auto DC inj. level 2] (SdC2) and [Auto DC inj. time 2] (tdC2) are not accessible. Only [Auto DC inj. time 1] (tdC1) can be accessed. This then corresponds to a zero speed maintenance time. t t Run command 1 0 t Speed 0 t (1) In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate. 62 AAV49426 04/2014