Download Functional Description Manual

Transcript
ECODRIVE03 SGP-01VRS
Supplement A: Serial Communications
1-23
Starting a command
Via the SIS interface all commands in the drive can be started with
Service 0x8F "write a parameter“.
Telegram head
Fig. 1-25:
User data
head
1 byte user data
Structure of the command telegram
• Enter 0x8F in the service of the telegram head.
• Enter the actuating command in parameter type and number bytes of
the user data head.
• Enter the default of the command in the user data head.
Possible commands in the drive
Command
Drive parameter
Parameter no. in
telegram
Drive-guided referencing
S-0-0148
0x0094
Reset C1D
S-0-0099
0x0063
Communications phase 3
transition check
S-0-0127
0x007F
Communications phase 4
transition check
S-0-0128
0x0080
Base load
S-0-0262
0x0106
Set absolute
measurement
P-0-0012
0x800C
Load base parameters
P-0-4094
0x8FFE
Communications phase 2
transition check
P-0-4023
0x8FB7
Set absolute dimension
emulator
P-0-4032
0x8FC0
Automatic control loop
P-0-0162
settings
Fig. 1-26: Commands in drive
0x80A2
Always set parameter type to 0x00. Thus only S and P parameters sare
possible.
Default in user data byte
Effects
0
clears command
3
Fig. 1-27:
Note:
DOK-ECODR3-SGP-01VRS**-FKB1-EN-P
starts command
Command default
Command status can be read by writing "0" into the first
element of the command parameter to be read.