Before starting a measurement, you can enter a text (maximum length 32 characters) as the description
of the measurement job. After transmitting the measured data to your computer, you can access this text
under “Comment 2.”
Special connection types for secondary converter systems:
This function has to be activated if the secondary voltage converters are connected in a medium
or high-voltage network as a V circuit. The voltage connection U2 is connected to earth.
The multilog 2 bases all trigger thresholds or PQ events on the set rated voltage.
The contractually agreed conductor – conductor voltage is specified as the rated voltage in the 3-wire
network, e.g. 20,400 V. In the 4-wire network, the conductor – earth voltage is specified as e.g. 230 V.
EDEBDA00140-2115-1_EN_multilog 2
The measurement interval of the multilog 2 can be freely set in the range between 1 and 1,800 seconds.
The basic setting is 10 minutes, as this is defined in the EN50160 and IEC61000-2-2 standards as interval
length.