2.24 @AADA Description : Disable Alarm Syntax : @AADA[CHK](cr) @ delimiter character AA address of setting module (00 to FF) DA command for disable alarm Response : Valid Command : !AA[CHK](cr) Invalid Command : ?AA[CHK](cr) Syntax error or communication error may get no response. ! delimiter for valid command ? delimiter for invalid command AA address of response module (00 to FF) Example : Command : @01DA Receive : !01 Disable address 01 alarm, return success. Related Command : Sec.2.21 @AAEAT Related Topic : Sec.3.6 High/Low Alarm Note : The command is for I-7012/12D/12F/12FD/14D only 48 I-7012, I-7014, I-7017 User Manual Rev:B1.2