Download LN1000 User Manual - MTL Instruments Group
Transcript
Write Multiple Request – Master START SYSTEM ADDR FUNC TIME Y 0x0F START ADDR HI Y START ADDR LO Y NUM COILS HI Y NUM COILS LO Y BYTE COUNT N Y DATA BYTES Y*N LRC ERROR CHECK YY STOP TIME System address Range is 0x00 (0) to 0xFE (254). Default is 0x00. Start address word HI/LO word Indentifies the address of the first data bit to be written. Only port coil data type can be written:First Port Coil Address = Start address + Port Offset. Default first coil address in system = 0 Number coils HI/LO word Number of coils to be written. Max number possible 1984. Byte Count Number of data Bytes sent. One data byte is sent for every 8 data bits “coils” written with a minimum of one data byte assuming at least one data bit “coil” is written. Data Bytes Each bit in a data byte represents a coil. Set Input abnormal: Data bit = HI. Set Input normal: Data bit = LO. Write Multiple Response – Slave START SYSTEM ADDR FUNC START ADDR HI START ADDR LO TIME Y 0x0F Y Y System address NUM INPUTS HI Y Range is 0x00 (0) to 0xFE (254). Default is 0x00. Start address HI/LO word Same as the original request. Number inputs HI/LO word Same as the original request. 92 NUM INPUTS LO Y LRC ERROR CHECK YY STOP TIME