„400 V Class
Table 9.2 400 V Class Inverters
Model Number
CIMR-L7Z †
43P7
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4055
3.7
4.0
5.5
7.5
11
15
18.5
22
30
37
45
55
Rated output capacity
(kVA)
7
9
12
15
22
28
34
40
54
67
80
106
Rated output current
(A)
8.5
11
14
18
27
34
41
48
65
80
96
128
115
154
Max. applicable motor out-
Output Rating
put (kW) *1
Max. output voltage
(V)
3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency
(Hz)
120 Hz max.
Rated voltage (V)
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
Power supply characteristics
Rated frequency (Hz)
Rated input current (A)
10.2
13.2
17
22
Allowable voltage
fluctuation
41
49
58
78
96
+ 10%, - 15%
Allowable frequency
fluctuation
DC reactor
Measures for
12-phase
power
rectification
supply
32
±5%
Optional
Built In
Not possible
Possible
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure
that the Inverter's rated current is higher than the motor's rated current.
* 2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
9