Download Display - Service, Support
Transcript
A Pinout A.3 Connector for Industrial Ethernet Pinning - 15-Pin Sub-D Female Connector Pin No. Signal Name Function 1 MEXT External ground, shield 2 CLSN Collision + 3 TRMT / TPETXD Transmit + / TPE Transmit Data + 4 Ground Ground 5 V 5 RCV / TPERXD Receive + / TPE Receive Data + 6 M 15 V Ground 15 V 7 TPE_SEL Switchover AUI/ITP 8 Ground Ground 5 V 9 CLSN_N Collision - 10 TRMT_N / TPEXTXD_N Transmit - / TPE Transmit Data - 11 Ground Ground 5 V 12 RCV_N / TPERXD_N Receive - / TPE Receive Data - 13 P15 V +15 V 14 Ground Ground 5 V 15 - - The pin assignment complies with IEEE 802.3 AUI interface. The signals TPETXD / TPETXD_N and TPERXD / TPERXD_N form the ITP interface. A.4 Connector for PROFIBUS 9-pin D-sub female connector for PROFIBUS (used with IE/PB Link) Pin No. 1 A -282 Signal Name PE PROFIBUS Designation Protective earth Used in RS485 yes 2 - - 3 RxD/TxD-P Data line B yes - 4 RTS (AG) Control-A - 5 M5V2 Data reference potential yes 6 P5V2 Power supply plus yes 7 BATT - 8 RxD/TxD-N Data line-A 9 - - yes - S7-CPs for Industrial Ethernet Configuring and Commissioning Release 09/2007 C79000-G8976-C182-08