Download 5600 - FM Global
Transcript
5600 April 2013 4.25.3.2 Test/Verification 4.25.3.2.1 Vibration Test The test sample shall be assembled in either the horizontal, lateral, or vertical orientation. The sample shall then be vibrated over the range of 10 – 60 Hz at intervals of 2 Hz at the table displacement specified below. Each frequency of vibration shall be maintained for 5 minutes. Table 4.25.3.2.1 Amplitude of Vibration Frequency of Vibration, hertz 10 – 19 20 – 39 40 – 60 Table Displacement Amplitude inch (mm) inch (mm) 0.060 ± 0.006 (1.52 ± 0.15) 0.030 ± 0.003 (0.76 ± 0.08) 0.040 ± 0.004 (1.02 ± 0.10) 0.020 ± 0.006 (0.51 ± 0.05) 0.020 ± 0.002 (0.51 ± 0.05) 0.010 ± 0.001 (0.25 ± 0.03) The sample shall subsequently be vibrated for 2 hours at the frequency that produced the maximum resonance observed during the initial vibration. If no resonance was initially observed, the sample shall be vibrated for 2 hours at a frequency of 60 Hz. In either case, the table displacement shall be as specified in Table 4.25.3.2.1. Following completion of the vibration test in the first plane, the test shall be repeated in the remaining two planes until the sample has been subjected to vibration tests in all three rectilinear orientation axes. 4.25.3.2.2 Shock Resistance Test The test sample shall be mounted on a shock machine and subjected to 5000 shock impacts. Each impact shall have an acceleration of 10g, or 322 ft/s2 (98 m/s2), and a duration of 20 – 25 milliseconds as measured at the base of the half sine shock envelope. 4.25.3.2.3 Vibration and Shock Resistance Post Tests Subsequent to the completion of the vibration and shock resistance tests, the sample shall be successfully discharged using one of the manufacturer’s compatible operating devices. The sample shall then be disassembled and visually inspected for damage. Mounting brackets shall be subjected to Section 4.13 (Mounting Device Test). 4.25.4 Nozzle Distribution Verification Tests For extinguishing systems or automatic extinguisher units that are limited by a maximum volume of protection, the performance requirements described in Section 4.2 (Nozzle Distribution Verification Tests) shall be repeated with an air flow equal to one air change per minute. For these tests, the test enclosures shall additionally include one 1 ft2 (0.09 m2) opening at the top of the enclosure, and one 1 ft2 (0.09 m2) opening within 2 ft (0.6 m) of the bottom of the enclosure; these opening sizes may not be scaled based on enclosure volume. The fan being used to provide the air exchange can either be located in the upper 1 ft2 opening, or in a separate opening, but not in the lower 1 ft2 opening. These tests shall be conducted at the design concentration, rather than the minimum extinguishing concentration. Testing shall performed in both the minimum room height test enclosure, which shall include the maximum area of coverage for the unit, and the maximum room height test enclosure, which shall include the maximum specified protected volume for the unit. The extinguisher shall be conditioned to 70ºF ±5ºF (21ºC ±1.8ºC) for these tests. FM APPROVALS 46