Download SmartAXIS Pro/Lite Users Manual
Transcript
2: PRODUCT SPECIFICATIONS Output Specifications (10A Relay) FT1AType Number H12RC B12RC H12RA B12RA H24RC B24RC H24RA B24RA No. of Outputs (Terminal No.) 4 (Q0 to Q3) Terminal Arrangement See "Terminal Arrangement" on page 2-16. Output Type 1a contact Maximum Load Current (Note) 10A Minimum Switching Load 10mA/5V DC (reference value) Initial Contact Resistance 100mΩ maximum (1A, 6V DC) Electrical Life 100,000 operations minimum (rated load 1,800 operations/hour) Mechanical Life 20,000,000 operations minimum (no load 18,000 operations/hour) Rated Load (Note) 250V AC/10A, 30V DC/10A Dielectric Strength Between output terminal and internal circuit: 2,300V AC, 1 minute Between output terminals (COMs): 2,300V AC, 1 minute Status Display Pro LCD display Lite — H40RC B40RC H40RKA H40RSA B40RKA B40RSA Note: Values for resistive/inductive load. Output Delay ON Command OFF ON Output Relay Status OFF OFF delay: 10ms maximum Chatter: 6ms maximum ON delay: 6ms maximum Derating When using the SmartAXIS at an operating temperature of 45°C or higher, reduce the output current of the 10A relay and power supply voltage as shown in the figure below. Normal Installation Output Current 10A Operating Temperature 4 5 °C Operating Temperature 5 5 °C 8A 0 Power Supply Voltage 24V 28.8V Note: UL, c-UL Listed at 0 to +50°C (FT1A Version V110). SMARTAXIS PRO/LITE USER'S MANUAL FT9Y-B1378 2-13