Download Series 982
Transcript
Setup-Output [`Ot2] Output 2 Set the way that output 2 will respond to a difference between the set point and an input variable. NOTE: [`Ot2] prompt will not appear if [SLid] is selected for [`In2]. • [`AL2] de-energizes output 2 in an alarm condition. • [AL2n] energizes output 2 in an alarm condition. • [``Ht] select reverse action, so that output 2 responds when the input signal is less than the set point. This prompt only appears if [`Ot1] is set to [``CL]. • [``CL] select direct action, so that output 2 responds when the input signal is more than the set point. This prompt only appears if [`Ot1] is set to [``Ht]. [`Ot2] This prompt appears only on controllers equipped with output 2 hardware (not 98__-___A-____). [`AL2] and [AL2n] do not appear if output 2 is a process output (98__-___F-____). [``Ht] and [``CL] do not appear if [AL90] (in the Global Menu) is set to [dUPL]. Default [Prc2] ↓ [``no] [`AL2] [Al2n] [`Ot2] [`Ot2] [`Ot2] [``Ht] or [``CL] [`Ot2] [`Ot2] Process 2 Select the process range for output 2. [Prc2] This prompt appears only on controllers equipped with output 2 process hardware (98__-___F-____) and with [`Ot2] not set to [``no]. Default ↓ Setup Menus, Chapter 4 4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc) [4-20] [0-20] [`0-5] [`1-5] [0-10] [Prc2] [Prc2] [Prc2] [Prc2] [Prc2] WATLOW Series 982 User’s Manual 4.15