PSI System Controls and Diagnostics 18 Fault-finding Symptom Possible Cause Incorrect analog input readings Cabling error Confirmation Solution Check signals are connected to Use appropriate connection. the correct pins. Calibration incorrect or corrupted Check calibration values. Unintentional or incorrect use of the application calibration. Check application calibration values and whether “Use temporary scaling” is checked. Incorrect analog output values Terminating impedance is too low. Disconnect load and remeasure. Ensure load is within the current compliance of the analog outputs. Outputs drop to zero SAFEstate is enabled and communication has been lost. Check setting and state of communications. Check connections to controller, status of controller. Use appropriate SAFEstate setting for the application. High noise levels Integration time too short for signal being measured Noise level reduces with integration period. Use an appropriate integration time for the signal level. Line voltage pickup Noise level drops sharply if Keep M40 and signal cables integration period is 16.7 msec clear of unscreened high (60 Hz) or 20 msec (50 Hz) current mains voltage. Use integration periods (N/line frequency) if possible. M40 User Manual M40_UM_150226 Page 54 of 62 Re-enter correct values, or contact supplier or Pyramid Technical Consultants, Inc. if no problem found.