SECTION 7
System Settings
Using BUSY Signals (Error Method)
The BUSY signal is a control signal used to show that the V530-R160 is busy processing. The ON/OFF
timing of this BUSY signal is monitored at the host device to time communications. The handling of the
BUSY signal can be changed to create a smoother system.
n Input in the BUSY Status
While reading processing is in progress (while the BUSY signal is ON), the controller will not read
image data even if TRIG A is input. Set whether or not the ERR signal is turned ON as notification that the host has not accepted a trigger.
Selection
Details
ERR ON*
When a TRIG A is input during processing (while the BUSY signal is ON), the
ERR signal turns ON and reading is not performed. The ERR signal will turn
OFF when the next TRIG A is input at the correct timing.
OFF
The ERR signal will not turn ON even if the TRIG A is input during processing.
Reading will not be performed.
The asterisk (*) indicates the default setting.
The BUSY signal turns OFF when the reading has been completed.
TRIG A
Image input
Reading
Display
OFF
BUSY
ON
Processing in progress
SECTION 7
1. Go into SYS (system) mode and select Error method.
Using BUSY Signals (Error Method)
Refer to page 180.
The Error method setting screen will be displayed.
2. Change the settings.
3. Select End.
The setting will be registered and the System mode screen will return.
V530-R160
Operation Manual
187