Tolerances
Current Transformer
Supervision CTS
ΔI
In order to prevent faulty
tripping of phase
selective protection
functions that use the
current as tripping
criterion. If the difference
of the measured earth
current and the
calculated value I0 is
higher than the pick up
value ΔI, an alarm event
is generated after
expiring of the excitation
time. In such a case, the
existence of a fuse
failure, a broken wire or a
faulty measuring circuit
can be assumed.
resetting ratio
t
Alarm delay
Range
Step range
Tolerance
0.1...1.0 x In
0.1 x In
±2% of the setting value
resp.1.5% In
94%
0.1...9999 s
0.1 x s
±1% resp. ± 10 ms
Voltage Transformer
Supervision VTS
ΔV
In order to prevent faulty
tripping of phase
selective protection
functions that use the
voltage as tripping
criterion. If the difference
of the residual voltage
and the calculated value
V0 is higher than the pick
up value ΔV, an alarm
event effected after the
excitation time. In such a
case, a fuse failure, a
broken wire or a faulty
measuring circuit can be
assumed.
resetting ratio
t
Alarm delay
Range
Step range
Tolerance
0.2...1.0 x Vn
0.2 x Vn
±2% of the setting value
resp.1.5% Vn
94%
0.1...9999 s
0.1 x s
±1% resp. ± 10 ms
Page 380
MRA4 02.08 UK