Download MRA4 HighPROTEC - DSF Technologies
Transcript
V-Protection Module – Voltage Protection [ANSI 27/59] If phase voltages are applied to the measuring inputs of the device and field parameter »VT con« is set to »Phase-to-neutral«, the messages issued by the voltage protection module in case of actuation or trip should be interpreted as follows: »V[1].ALARM L1« or »V[1].TRIP L1« => alarm or trip caused by phase voltage »VL1«. »V[1].ALARM L2« or »V[1].TRIP L2« => alarm or trip caused by phase voltage »VL2«. »V[1].ALARM L3« or »V[1].TRIP L3« => alarm or trip caused by phase voltage »VL3«. If, however, line-to-line voltages are applied to the measuring inputs and field parameter »VT con« is set to »Phase to Phase«, then the messages should be interpreted as follows: »V[1].ALARM L1« or »V[1].TRIP L1« => alarm or trip caused by line-to-line voltage »V12«. »V[1].ALARM L2« or »V[1].TRIP L2« => alarm or trip caused by line-to-line voltage »V23«. »V[1].ALARM L3« or »V[1].TRIP L3« => alarm or trip caused by line-to-line voltage »V31« For each of the voltage protection stages it can be defined if it should be actuated in case over- or undervoltage was detected in all three phases, or if it already should be alarmed when the over- or undervoltage was detected in only one of the phases. MRA4 02.08 UK Page 275
Related documents
MRA4 HighPROTEC
Instruction Manual
Eton 4000 Plus Instruction manual
SonicWALL TZ 170 10 Node with Comprehensive Gateway Security
SonicWALL TZ 170 10 Node
DELL Force10 S6000
Scarica - 24 oktober 2015.
Application to compile the monitoring plan to monitor the
Istruzioni per l`uso NJ1 e
AUTOTEST USER MANUAL 2.0
Präsentation Energy Labels
instructions