I2>-Protection Module – Unbalanced Load Protection [ANSI 46]
Legend:
t = Tripping delay
t -cool = Cooling time constant
Theta(t) = Momentanous heat (thermal) energy
Theta 0 = Heat (thermal) energy before the cooling down has started
If the heat amount is not reduced when the permitted unbalanced load current is overshoot again, the remaining
heat amount will cause an earlier tripping.
Typical NPSI-Relay Operating Curves
100001 . 104
1 . 10
3
t ( I2% , 0.5 , 200)
t ( I2% , 0.5 , 100)
100
Time (s)
t ( I2% , 0.5 , 50)
t ( I2% , 0.5 , 20)
t ( I2% , 0.5 , 10)
t ( I2% , 0.5 , 5)
t ( I2% , 0.5 , 1)
10
1
0.1
0.1
1
10
1
I2%
(Curren t I2/I2s (%))
10
K=200
K=100
K=50
K=20
K=10
K=5
K=1
MRA4 02.08 UK