Tolerances Current Transformer Supervision CTS ΔI In order to prevent faulty tripping of phase selective protection functions that use the current as tripping criterion. If the difference of the measured earth current and the calculated value I0 is higher than the pick up value ΔI, an alarm event is generated after expiring of the excitation time. In such a case, the existence of a fuse failure, a broken wire or a faulty measuring circuit can be assumed. resetting ratio t Alarm delay Range Step range Tolerance 0.1...1.0 x In 0.1 x In ±2% of the setting value resp.1.5% In 94% 0.1...9999 s 0.1 x s ±1% resp. ± 10 ms Voltage Transformer Supervision VTS ΔV In order to prevent faulty tripping of phase selective protection functions that use the voltage as tripping criterion. If the difference of the residual voltage and the calculated value V0 is higher than the pick up value ΔV, an alarm event effected after the excitation time. In such a case, a fuse failure, a broken wire or a faulty measuring circuit can be assumed. resetting ratio t Alarm delay Range Step range Tolerance 0.2...1.0 x Vn 0.2 x Vn ±2% of the setting value resp.1.5% Vn 94% 0.1...9999 s 0.1 x s ±1% resp. ± 10 ms Page 380 MRA4 02.08 UK