Download SCADAPack E Target 5 Technical Reference
Transcript
16 5.1 SCADAPack E Target 5 Technical Reference Continuous Scanning This is the default Execution Mode that is used by IEC 61131-3 resources (application programs). This mode is enabled if the resource's Execution Mode property is set to Real Time and the Cycle Time is set to zero. If enabled, at the end of an IEC 61131-3 target scan, the target simply restarts the scanning cycle. Typically, the SCADAPack E RTU has many activities it needs to perform in addition to scanning the user’s IEC 61131-3 application. As such, the application may be interrupted for short periods throughout the scan cycle. This can result in some variations in the time it takes the VM to perform each scan. If the RTU becomes unusually busy performing these activities, this can result in slower execution of the user’s IEC 61131-3 application. Resource Execution Mode property This mode can be temporarily overridden from within the SCADAPack Workbench debugger. The debugger can be used to change to Cycle Time Scanning 18 by writing a new value to the __SYSVA_TCYCYCTIME 18 resource global TIME variable. WARNING UNINTENDED EQUIPMENT OPERATION Evaluate the operational state of the equipment monitored and controlled by the RTU before debugging. Hazardous situations can occur if system state is not confirmed prior to debugging. Failure to follow these instructions can result in death, serious injury or equipment damage. If the IEC 61131-3 application or the SCADAPack E RTU is restarted, a temporary cycle timing setting is lost. The cycle time will revert to the Resource properties’ Execution Mode and Cycle Time settings.