(1) The list of the conditions to detect disconnection (no connection) or a shortcircuit (ground) of a sensor power supply The locations where the detection is possible (1) to 9)) and the detection conditions are shown below. (a) AJ65ABTP3-16D AJ65ABTP3-16D Input device 3) COM+ COM+ 9) 8) 7) External power supply Internal control circuit 1) Xn Detection circuit 6) 5) 2) Short-circuit detection circuit -Cn 4) COM- FG: Device frame Disconnection Connected Condition device 2-wire input device 3-wire input device Xn -Cn COM+ -CnFG Xn-Cn XnFG -CnCOM+ XnCOM+ COM+FG 1) 2) 3) 4) 5) 6) 7) 8) 9) *2 × *2*3*4 - - - *2 × *2*3*4 *3*4 × Leakage current (higher than 0.3mA) Leakage current (0.3mA or lower) Holding current (higher than 0.3mA) Holding current (0.3mA or lower) Short-circuit (ground) (no connection) *1 *1 - × × *1 *1 : Detection is possible, *1 *2 *3 *4 : Detection is possible depending on conditions, ×: Detection is not possible Bleeder resistances must be connected in parallel just proximal to the input device. (Allowable bleeder resistance: 56k) The positive common (COM+) of the external power supply must be connected to the device frame. The detection is possible when the connected input device is turned on. For some input devices, the short-circuit cannot be detected because the short-circuit current does not flow due to the short-circuit protection function. If a short-circuit occurs, remove the cause immediately. If the short-circuit remains, the internal temperature of the module rises, resulting in malfunction or failure. 38