AXN-STR User Manual 3.2
7.7
PV Charging Condition
PV Charging is NOT affected by above mode setting, but it is activated when below two conditions are achieved.
Condition
1
PV Voltage
(PV_Charge)
2
Battery Voltage
(Batt_Charge)
Voltage
>170V~ 500V
Status
start charging
<150V
stop charging
>420V
stop charging
<405V
start charging
7.8
Interaction Between Modes
The modes interaction is limited to certain combinations:
1) When Charge Mode is Mode1 or Mode3 (Timer On), On Grid/Off Grid1/Off Grid2 Mode is not allowed to
function.
(Battery can NOT feed into either load or grid when being charged by AC power.)
2) When Off Grid1/Off Grid2 Mode is Mode1 or Mode3 (Timer On), On Grid Mode is not allowed to function.
(Battery can NOT supply load and grid at the same time.)
3) The order of preference the system set is
Charge Mode>Off Grid1/Off Grid2 Mode>On Grid mode