Download INSTAllATION MANUAl
Transcript
programming Vibration Sensitivity P30E – P36E Program Mode level Installer mode or NessComms. Each zone has individually adjustable sensitivity for connection of Nessensor Vibration Sensors. Zone sensitivity is adjusted by toggling zones ON in options P30E to P36E. P30E is Normal Sensitivity, vibration analyser disabled. This is used for normal alarm devices. Zone response time, 200ms. Factory Default Normal sensitivity. P30E, all zones = ON. P31–36E are the options for the 6 levels of vibration sensitivities. P31E is the most sensitive setting. Notes • Sensitivity can be individually programmed for each zone. Programming sequence: P [30–38] E zones are displayed [Zone No] E • Zones are allocated to one sensitivity level at any one time. Turning a zone ON in a sensitivity level, turns the zone OFF in any other sensitivity level. EXAMPLE: To program zones 2 and 3 to be Medium sensitivity: P34E 2E 3E the keypad display will show zone lights 2 & 3 on. • To revert zone sensitivity back to Normal, turn on the required zone/s at P30E. For compatibility with existing installations, the sensitivity levels P31E to P36E are identical to previous versions of D8/D16. Vibration Options Sensitivity Level "Extreme" (P31E) is provided as a guide to the upper limit and should NOT be used. Zones 1–8 (D8 & D16) 1 Option No. Description P30E Normal P31E Vibration Extreme* P32E Vibration Highest P33E Vibration High P34E Vibration Medium P35E Vibration LowEr P36E Vibration LOWest P37E 1 second zones P38E 3 second zones 2 3 4 5 6 7 Zones 9–16 (D16) 8 9 10 11 12 13 14 15 16 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON * Extreme sensitivity (P31E) should not be used. It is provided as a guide only Adjusting NESSENSORS Nessensors are sensitive to high frequencies and insensitive to low frequencies. Therefore it is not necessary to apply much force to the protected structure, rather a very rapid succession of blows. The sensitivity has been correctly adjusted when a single blow applied with a soft object (e.g. by hand) does not cause an alarm whereas a rapid series of blows (using a metal object such as a screwdriver blade) will cause an alarm. P37E – P38E NESSENSOR™ Vibration Sensor Part No. VIB500 In addition to zone sensitivity adjustment, the overall sensitivity of the Nesssensor can be adjusted by rotating the body of the Nesssensor within its bracket. L M H L L M H L L M H L L M H L M L L H The Nessensor bracket must always be mounted horizontally and the arrow must point up for any required setting. Long Response Zones Program Mode level Installer mode or NessComms. Factory Default all off Notes • A Long Response Zone cannot be a Normal Zone or Vibration zone at the same time. • To convert zone/s back to a Normal Zone, turn on the required zone/s at P30E. Long Response Zones are normal alarm zones with a long reaction time. Individual zones can be programmed to have either a 1 second response (P37E) or 3 second response (P38E). This is useful where zones 5, 6 or 7 have been programmed as REX inputs for access control purposes, (P301E 5E-7E). To prevent accidental door opening, the REX button then must be pressed and held for 1sec or 3sec, as programmed. Programming sequence: P37E or P38E [Zone No]E toggles zones ON and OFF RELATED OPTIONS P301E 5E-7E Request To Exit (REX) Ness D8x / D16x DELUXE Control Panel – Installation Manual 17