7. Setting NIBE FLM
8. Setting the fan speed exhaust air
start guide 5.7
FLM :
fan sp. exhaust air :
continuous pump op.
time between defrosts
start guide 5.7
hrs
months btwn filter alarms
This part of the start guide is only displayed if the alternative is selected in a previous menu and the accessory is
installed.
normal
%
speed 1
%
speed 2
%
speed 3
%
speed 4
%
This part of the start guide is only displayed if the alternative is selected in a previous menu and the accessory is
installed.
time between defrosts
normal and speed 1-4
Setting range: 1 – 30 h
Setting range: 0 – 100 %
Default value: 10 h
months btwn filter alarms
Set the speed for the five different selectable speeds for
the fan here.
Setting range: 1 – 12
Default value: 3
continuous pump op.: Select for continuous operation
of the circulation pump in NIBE FLM.
Caution
Too low a value can damage the house in the
long term.
time between defrosts: Set the minimum time that
must pass between defrostings of the heat exchanger in
NIBE FLM.
When the exhaust air module is in operation the heat
exchanger is cooled so that ice builds up on it. When too
much ice builds up the heat transfer capacity of the heat
exchanger is reduced and defrosting is required. Defrosting warms up the heat exchanger so that the ice melts
and runs off via the condensation hose.
months btwn filter alarms: Set how many months
should pass before the heat pump informs that it is time
to clean the filter in NIBE FLM.
Clean NIBE FLM's two air filters regularly, how often depends on the amount of dust in the ventilation air.
30
Chapter 6 | Commissioning and adjusting
NIBE™ F1245