21. Complete the start guide
start guide 5.7
You have come to the last page of the start
guide. Do you wish the start guide to start the
next time the heat pump is restarted?
yes
no
Here you select whether to start the start guide the next
time the heat pump is restarted.
Caution
If you choose "yes" this means that the next
time the heat pump is started (e.g. after a power
cut) it will not produce heat or hot water.
Post adjustment and venting
Pump capacity diagrams, collector side
To set the correct flow in the brine system the correct
speed must be set for the brine pump.
The flow must have a temperature difference between
brine out (BT11) and brine in (BT10) of 2 - 5 °C when the
system is balanced (suitably 5 minutes after compressor
start). Check these temperatures in menu 3.1 "service
info" and adjust the brine pump (GP2) speed until the
temperature difference is achieved. A high difference indicates a low brine flow and a low difference indicates a
high brine flow.
Check that the correct program ("Proportional pressure")
is set on the brine pump (GP2). Only the LED for "Proportional pressure" should light around the program selector.
If it must be reset press the program selector repeatedly
until the correct LED lights (see illustration).
Set the speed of the brine pump by pressing the “Increase” or "Reduce" button. Hold the "Increase" button
to set "Max" speed.
Read off what speed the brine pump should have from
the diagrams below.
Increase
M
AX
Reduce
STOP
100%
Q
EXT
AUTO
ADAPT
Program selector
Proportional
pressure
P
36
Chapter 6 | Commissioning and adjusting
Tillgängligt
tryck
Available
pressure
Electrical
Eleffekt output
NIBE™ F1245