Download Arctic Substation Gateway User Manual
Transcript
User Manual Arctic Substation Gateway 7 IEC-104 application settings The IEC-104 and IEC-101 protocols share the same ASDU level messaging but differ on the link level. The IEC-104 is intended for packet-switched TCP/ IP communication whereas the IEC-101 is intended for serial communication. By using the Arctic Substation Gateway, the IEC-101 slaves (e.g. RTUs) can be connected to a IEC-104 master (e.g. SCADA). The Arctic requests event from the IEC-101 slave locally and sends them to the IEC-104 master. This eliminates the need to continuously poll the data remotely and therefore reduces the communication costs on pay-per-use wireless network. This approach also eliminates the IEC-101 parameter adjutancy problems caused by variable round-trip delays on wireless networks and makes the information exchange faster and more reliable. You can view and change the application settings in Applications > IEC-104 (RSx). Figure 26. IEC-104 Application Settings 7.1 General settings IEC-104 gateway enabled Enables or disables IEC-104 to IEC-101 gateway functionality. Table 18: IEC-104 gateway enabled IEC-104 gateway enabled Type Boolean Units N/A Firmware Version 2.4.x 34 Document Version 1