Download Micrologic - Schneider Electric
Transcript
Technical appendix Measurement setting ranges and accuracy b The accuracy of the current measurements depends on both the value displayed (or transmitted) and the circuit-breaker rating, where: Accuracy = 0.5 % In + 1.5 % reading Measurement setting ranges and accuracy Example: For a circuit breaker with a 4000 A rating and a current displayed on Micrologic of 49 A, the accuracy is: 0.5 % x 4000 + 1.5 % x 49 = ±21 A Type Instantaneous current I1, I2, I3 IN I t ground I t earth leakage I1 max, I2 max, I3 max IN max I t max ground I t max earth leakage Demand current I1, I2, I3 IN I1 max, I2 max, I3 max IN max Phase-to-phase voltages U12 U23 U31 Phase-to-neutral voltages V1N V2N V3N Average voltage U avg Voltage unbalance U unbal Instantaneous power P Q S Power factor PF Demand power P Q S P max Q max S max Total energy E.P E.Q E.S Total energy in E.P E.Q Total energy out E.P E.Q Frequency F 86 Range Accuracy at 25 °C 0.05 x In to 20 x In 0.05 x In to 20 x In 0.05 x In to In 0 to 30 A 0.05 x In to 20 x In 0.05 x In to 20 x In 0.05 x In to In 0 to 30 A ±1.5 % ±1.5 % ±10 % ±1.5 % ±1.5 % ±1.5 % ±10 % ±1.5 % 0.05 x In to 20 x In 0.05 x In to 20 x In 0.05 x In to 20 x In 0.05 x In to 20 x In ±1.5 % ±1.5 % ±1.5 % ±1.5 % 170 to 1150 V 170 to 1150 V 170 to 1150 V ±0.5 % ±0.5 % ±0.5 % 100 to 1150 V 100 to 1150 V 100 to 1150 V ±0.5 % ±0.5 % ±0.5 % 170 to 1150 V ±0.5 % 0 to 100 % ±0.5 % 0.015 to 184 MW 0.015 to 184 Mvar 0.015 to 184 MVA ±2 % ±2 % ±2 % -1 to +1 ±2 % 0.015 to 184 MW 0.015 to 184 Mvar 0.015 to 184 MVA 0.015 to 184 MW 0.015 to 184 Mvar 0.015 to 184 MVA ±2 % ±2 % ±2 % ±2 % ±2 % ±2 % -1010 GWh to +1010 GWh -1010 Gvarh to +1010 Gvarh -1010 GVAh to +1010 GVAh ±2 % ±2 % ±2 % -1010 GWh to +1010 GWh -1010 Gvarh to +1010 Gvarh ±2 % ±2 % -1010 GWh to +1010 GWh -1010 Gvarh to +1010 Gvarh ±2 % ±2 % 45 Hz to 440 Hz ±0.1 % 04443726AA - 09/2009