Table 6.1 Error Code List (Continue)
Error
Massage
Detailed
Error
Error
CPU
Code
Code
States
(D9008)
(D9091)
"INSTRCT
CODE
ERR"
107
10
Error and Cause
(1) Index qualification is
specified for the
device numbers and
set values in the
OUT instruction of
timers and counters.
(2) Index qualification is
specified at the label
number of the
pointer (P) provided
to the head of
destination of the
STOP
CJ , SCJ , CALL ,
CALLP , JMP ,
LEDA/B FCALL and
Corrective Action
Read the error step using
a peripheral device and
correct the program of
the step.
LEDA/BBREAK
(Checked
when
STOP
RUN or at
execution
of
instruction.)
108
"PARAMET
ER
ERROR"
111
11
112
(Checked
at power on
and at
STOP/
PAUSE
RUN.)
113
114
instructions or at the
label number of the
interrupt pointer (I)
provided to the head
of an interrupt
program.
Errors other than 101 to
107 mentioned above.
Capacity settings of the
main and sub programs,
microcomputer program,
file register comments,
status latch, sampling
trace and extension file
registers are not within
the usable range of the
CPU.
Total of the set capacity
STOP of the main and sub
programs, file register
comments, status latch,
sampling trace and
extension file registers
exceeds capacity of the
memory cassette.
Latch range set by
parameters or setting of
M, L or S is incorrect.
Sum check error
94
Read parameters in the
CPU memory, check the
contents, make
necessary corrections
and write them again to
the memory.