Download QCPU(A mode) CPU Module User`s Manual
Transcript
3.2.3 Power supply The insulation specification of the power module was designed assuming installation category II. Be sure to use the installation category II power supply to the programmable controller. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability. Category IV Category III Category II Category I Figure 1. : Installation Category Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution. 3.2.4 Control panel Because the programmable controller is an open device (a device designed to be stored within another module), be sure to use it after storing in the control panel.* * Also, each network remote station needs to be installed inside the control panel. However, the waterproof type remote station can be installed outside the control panel. (1) Electrical shock prevention In order to prevent persons who are not familiar with the electric facility such as the operators from electric shocks, the control panel must have the following functions : (a) The control panel must be equipped with a lock so that only the personnel who has studied about the electric facility and have enough knowledge can open it. (b) The control panel must have a structure which automatically stops the power supply when the box is opened. (c) For electric shock protection, use IP20 or greater control panel. 26