EDS800 series Service Manual
(1) To get better control characteristic,suggest that the ratio of carrier frequency to inverter max. run
frequency be not smaller than 36.
(2) Error exists in current displayed value when carrier frequency is small.
note
F2.06
Jog run frequency
Range:0.10-50.00Hz
5.00Hz
F2.07
Jog Acc time
Range:0.1-60.0s
20.0s
F2.08
Jog Dec time
Range:0.1-60.0s
20.0s
Jog frequency has the highest priority. Under any status, the inverter would
transit to run at jog frequency at once according to set jog accelerating,
decelerating time as long as jog command is inputted, as shown in Fig.6-11.
Jog accelerating time means time during which the inverter accelerate from 0Hz
to high limit frequency,Jog Dec time means time during which the inverter
decelerate from high limit frequency to 0Hz.
Jog
freq.
Jog decelerating time
Jog accelerating
time
Jog
freq.
Jog.
signal
Jog.
signal
Fig.6-11 jog run
note
(1) Keypad, control terminal and serial port can do jog control all.
(2) The inverter will stop according to Dec stop mode after jog run command is withdrawn.
F2.09
Freq. input channel combination
0: VCI+CCI
1: VCI-CCI
2: reserved
3: reserved
4: reserved
5: reserved
6: external pulse provision+CCI
7: external pulse provision-CCI
8: reserved
9: reserved
61
Range:0~28
0