EDS800 series Service Manual
Decelerating time is too
Prolong decelerating time
short
Increase braking power of
Have potential energy
external energy consumption
load or big inertia load
braking subassembly
E005
overvoltage
during
decelerating
process
E006
Accel/Decel time is set
Overvoltage
to too short
during constant
speed process Input voltage change
abnormally
Unwonted input voltage
E007
controlpower
supply
overvoltage
Use energy consumption
subassembly
Unwonted input voltage
Check input power supply or look for
service
improper V/F curve
Inverter
overload
Restart rotating motor
power source voltage is
too low
E009
Motor overload
Assemble reactor
Load inertia is a bit big
Accel time is set to too
short
DC injection braking is
too big
E008
Check input power supply
Prolong accelerating decelerating
time properly
Prolong accelerating time
Reduce DC injection braking
current,prolong braking time
Adjust V/F curve and torque
boost
Set speed checking restart
function
check power source voltage
Load is too big
Choose inverter with high-power
improper V/F curve
Adjust V/F curve and torque
boost
power source voltage is
too low
check power source voltage
General motor run at low
speed with big load
Can choose frequency conversion
motor for long time low speed
run
motor overload
to set motor overload protection
protection factor set
factor correctly
incorrectly
motor blocked up or load
change too suddenly and
Check the load
quickly
To clear air-path or improve
Air-path blocked
ventilation condition
over Ambient temperature is too Improve ventilation condition,
high
lower carrier frequency
E010
inverter
heating
E011
reserved
reserved
reserved
E012
reserved
reserved
reserved
Fan damaged
Replace the fan