Download User Manual
Transcript
EDS800 series Service Manual connected inverters increasing, following wiring is recommended: EDS800 EDS800 CPU board CPU board Mainframe Submachine Submachine 485A 485B 485A 485B 485A 485B Fig. 3-13 EDS800 … CPU board recommended wiring for multiple inverters communication (all inverters and motors well earthed) Normal communication still not available if using above wiring, can try to take following measure: 1> Provide separate power supply for PLC (or upper machine) or isolate its power supply. 2> Apply magnetic circle on the communication wire. 3> Reduce inverter carrier wave frequency properly. note 3.7 (1) When form the network only by inverters, you must set local address parameter F2.15 of the mainframe EDS800 to 0. (2) For programming of RS485 interface , please refer to chapter 10 MODBUS communication protocol. Installation guide for anti-jamming Main circuit of the inverter is composed of high-power semiconductor switch gear, so some electromagnetic noise will arise during work,to reduce or stop disturbance to environment,show you assembling method of inverter disturbance suppressing from many aspects such as disturbance suppressing, spot wiring, system grounding, leak current, usage of power supply filter etc. in this section to be referred to during spot assembling. 3.7.1 Restraining to noise disturbance Disturbance brought by the working inverter may affect nearby electronic device, effect degree relates to surrounding electromagnetic environment of the inverter and anti-disturbance capacity of this device. (1) type of disturbance noise According to work principle of the inverter, there are mainly 3 kinds of noise disturbance source: 1> circuit conduction disturbance; 2> space emission disturbance; 20