Download User Manual
Transcript
EDS800 series Service Manual 30 Run command channel selection 2 31 Run command channel selection 3 32 Traverse runin 33 External interruption input 34 interior counter clearing end 35 interior counter triggering end 36 Interior timer clearing end 37 interior timer triggering end 38 Pulse frequency input( only effective for X5) 39 Reserved 40 Reserved 41 Reserved 42 Reserved Now explain listed function in Table 6-3 as follows: 1~4: Multi-step speed control terminal. Can set 15 step speed run frequency by choosing ON/OFF combination of these function terminal. Table 6-4 multi-step speed run selection table K4 K3 K2 K1 Frequency setting OFF OFF OFF OFF Common run frequency OFF OFF OFF ON Multi-step frequency 1 OFF OFF ON OFF Multi-step frequency 2 OFF OFF ON ON Multi-step frequency 3 OFF ON OFF OFF Multi-step frequency 4 OFF ON OFF ON Multi-step frequency 5 OFF ON ON OFF Multi-step frequency 6 OFF ON ON ON Multi-step frequency 7 ON OFF OFF OFF Multi-step frequency 8 ON OFF OFF ON Multi-step frequency 9 ON OFF ON OFF Multi-step frequency 10 ON OFF ON ON Multi-step frequency 11 ON ON OFF OFF Multi-step frequency 12 ON ON OFF ON Multi-step frequency 13 ON ON ON OFF Multi-step frequency 14 ON ON ON ON Multi-step frequency 15 Above multi-step frequency can be used in multi-step speed run and simple PLC run, please see below an example of multi-step speed run: We now define control terminal X1, X2, X3, X4 separately as follows: After set F5.00=1, F5.01=2, F5.02=3, F5.03=4, X1, X2, X3, X4 are used for realizing multi-step run,as shown in Fig.6-26. 82