ing wireless component operates on Channel 17, you will want to
disable Channel 17 in the reader channel configuration. See “Assigning Reader Channels”.
Beacon Time — The default Beacon Time for a reader is one minute;
however, you can manually input a different value anywhere from 10
seconds to 1 day. Keep in mind, the more frequent the beacon time,
the more battery power used.
Note
For best results, it is recommended that beacon time be set to no
lower than 1 minute.
Default Operate Time — The Default Operate time is three seconds. You
can manually enter a different value as needed.
Default Shunt Time — The Default Shunt Time is three seconds. You
can manually enter a different value as needed. This feature is useful
for readers that will be used to accommodate wheelchairs or other
equipment that may need additional time to get through the door
before the alarm is triggered.
Operate Delay — This feature is useful during situations where, for example, a guard may want a chance to visually confirm the identity of
the user before access is granted.
Shunt Delay — This feature is useful when the users accessing this
reader typically need more time to pass through the door after it unlocks; such as, someone in a wheelchair or someone who will move
equipment through the doorway.
Statistics Update Interval — Manually enter the desired reader polling time.
Wiegand Device — Define if applicable.
Assigning Reader Channels
Perform the following steps to assign reader channels.
1 In the Reader tab, select the desired reader within the Segment Tree.
2 In the Reader Properties sheet, under the Configuration category,
click in the Assigned to Channels field. The ellipsis button appears
at the far right of the field.
3 Click the ellipsis button to display the Channel Selection for the
Reader.
93