Download Installation and Operating Instructions
Transcript
Operation Scaling the current output The current output setup mode is used to create current output scales for the first and second (if ordered) outputs that meet your requirements. You must define: 1. Output function function C.3.1.0 (output 1-distance) function C.4.1.0 (output 2-other: interface distance?) 2. 4 mA setting function C.3.2.0 (output 1) function C.4.2.0 (output 2) 3. 20 mA setting function C.3.3.0 (output 1) function C.4.3.0 (output 2) 4 and 20 mA settings are defined in terms of distance from the tank bottom or tank bottom offset. These are the minimum and maximum points of your measuring scale. Using the optional second output, you can set up a separate scale for measuring interface. Volume or mass measurement Volume/Mass table function C.1.21.0 101