Download Service Manual - Air
Transcript
6HUYLFH0DQXDO 02'(/A16CM4H4R18 A16CM4H4R24 A16CM4H4R30 5HIULJHUDQW5$ 7DEOHRI&RQWHQWV 7DEOHRI&RQWHQWV 6XPPDU\DQG)HDWXUHV 6DIHW\3UHFDXWLRQV 6SHFLÀ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nstalling, starting up, and servicing air conditioner can be hazardous due to system pressure, electrical components, and equipment location, etc. Only trained, qualified installers and service personnel are allowed to install, start-up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. Make sure the outdoor unit is installed on a stable, level surface with no accumulation of snow, leaves, or trash beside. When handling the equipment, observe precautions in the manual and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses andwork gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Follow all the installation instructions to minimize the risk of damage from earthquakes, typhoons or strong winds. Read the instructions thoroughly and follow all warnings or cautions in literature and attached to the unit. Consult local building codes and current editions of national as well as local electrical codes. Recognize the following safety information: Warning Incorrect handling could result in personal injury or death. Caution Incorrect handling may result in minor injury,or damage to product or property. Warning All electric work must be performed by a licensed technician according to local regulations and the instructions given in this manual. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Never supply power to the unit unless all wiring and tubing are completed, reconnected and checked. This system adopts highly dangerous electrical voltage. Incorrect connection or inadequate grounding can cause personal injury or death. Stick to the wiring diagram and all the instructions when wiring. Have the unit adequately grounded in accordance with local electrical codes. Have all wiring connected tightly. Loose connection may lead to overheating and a possible fire hazard. All installation or repair work shall be performed by your dealer or a specialized subcontractor as there is the risk of fire, electric shock, explosion or injury. Make sure the ceiling/wall is strong enough to bear the weight of the unit. Make sure the noise of the outdoor unit does not disturb neighbors. Avoid contact between refrigerant and fire as it generates poisonous gas. Apply specified refrigerant only. Never have it mixed with any other refrigerant. Never have air remain in the refrigerant line as it may lead to rupture and other hazards. Make sure no refrigerant gas is leaking out when installation is completed. Should there be refrigerant leakage, the density of refrigerant in the air shall in no way exceed its limited value, or it may lead to explosion. Keep your fingers and clothing away from any moving parts. Clear the site after installation. Make sure no foreign objects are left in the unit. Always ensure effective grounding for the unit. Caution Never install the unit in a place where a combustible gas might leak, or it may lead to fire or explosion. Make a proper provision against noise when the unit is installed at a telecommunication center or hospital. Provide an electric leak breaker when it is installed in a watery place. Never wash the unit with water. Handle unit transportation with care. The unit should not be carried by only one person if it is more than 20kg. Never touch the heat exchanger fins with bare hands. Never touch the compressor or refrigerant piping without wearing glove. Do not have the unit operate without air filter. Should any emergency occur, stop the unit and disconnect the power immediately. Properly insulate any tubing running inside the room to prevent the water from damaging the wall. 6SHFL¿FDWLRQV 6SHFLÀFDWLRQV 3DUDPHWHU 8QLW 9DOXH 0RGHO A16CM4H4R18 3URGXFW&RGH &%: 5DWHG9ROWDJH 3RZHU 6XSSO\ 5DWHG)UHTXHQF\ 9̚ +] 3KDVHV 3RZHU6XSSO\0RGH 2XWGRRU &RROLQJ&DSDFLW\0LQ ̚ 0D[ %WXK a +HDWLQJ&DSDFLW\0LQ ̚ 0D[ %WXK a &RROLQJ3RZHU,QSXW0LQ ̚ 0D[ : a +HDWLQJ3RZHU,QSXW0LQ ̚ 0D[ : a 6((5 %WXZK +63) %WXZK 6SHFL¿FDWLRQV 0,768%,6+,(/(&75,&*8$1*=+28&2035(6625 &2/7' &RPSUHVVRU0DQXIDFWXUHU7UDGHPDUN &RPSUHVVRU0RGHO 61%)*<0& &RPSUHVVRU2LO 39()96 &RPSUHVVRU7\SH 5RWDU\ /5$ $ &RPSUHVVRU5/$ $ &RPSUHVVRU3RZHU,QSXW : 2YHUORDG3URWHFWRU 7KURWWOLQJ0HWKRG (OHFWURQH[SDQVLRQYDOYH 2SHUDWLRQWHPS & a $PELHQWWHPSFRROLQJ & a $PELHQWWHPSKHDWLQJ & &RQGHQVHU)RUP a $OXPLQXP)LQFRSSHU7XEH 3LSH'LDPHWHU PP ĭ 5RZV¿Q*DS PP &RLO/HQJWK/;';: PP ;; )DQ0RWRU6SHHG USP : $ 2XWSXWRI)DQ0RWRU 2XWGRRU )DQ0RWRU5/$ 8QLW )DQ0RWRU&DSDFLWRU $LU)ORZ9ROXPHRI2XWGRRU8QLW ȝ) PK )DQ7\SH )DQ'LDPHWHU $[LDOÀRZ PP 'HIURVWLQJ0HWKRG 7 ,VRODWLRQ , 0RLVWXUH3URWHFWLRQ 3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUHIRU WKH'LVFKDUJH6LGH 3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUHIRU WKH6XFWLRQ6LGH ĭ $XWRPDWLF'HIURVWLQJ &OLPDWH7\SH ,3 03D 03D 6RXQG3UHVVXUH/HYHO+0/ G%$ 6RXQG3RZHU/HYHO+0/ G%$ 'LPHQVLRQ:;+;' PP ;; 'LPHQVLRQRI&DUWRQ%R[/:+ PP ;; 'LPHQVLRQRI3DFNDJH/:+ PP ;; 1HW:HLJKW NJ *URVV:HLJKW NJ 5HIULJHUDQW 5$ 5HIULJHUDQW&KDUJH NJ /HQJWK P JP *DV$GGLWLRQDO&KDUJH &RQQHFWLRQ2XWHU'LDPHWHU/LTXLG3LSH 3LSH 2XWHU'LDPHWHU*DV3LSH 17/ PP ĭ PP ĭ 0D['LVWDQFH+HLJKW P 0D['LVWDQFH/HQJWK P 6SHFL¿FDWLRQV 3DUDPHWHU 8QLW 9DOXH 0RGHO A16CM4H4R24 A16CM4H4R30 3URGXFW&RGH &%: &%: 9̚ +] 5DWHG9ROWDJH 3RZHU 6XSSO\ 5DWHG)UHTXHQF\ 3KDVHV 3RZHU6XSSO\0RGH 2XWGRRU 2XWGRRU &RROLQJ&DSDFLW\0LQ ̚ 0D[ %WXK a a +HDWLQJ&DSDFLW\0LQ ̚ 0D[ %WXK a a &RROLQJ3RZHU,QSXW0LQ ̚ 0D[ : a a +HDWLQJ3RZHU,QSXW0LQ ̚ 0D[ : a a &RROLQJ3RZHU&XUUHQW $ +HDWLQJ3RZHU&XUUHQW $ 5DWHG,QSXW : 5DWHG&XUUHQW $ 6((5 %WXZK +63) %WXZK 6SHFL¿FDWLRQV &RPSUHVVRU0DQXIDFWXUHU7UDGHPDUN &RPSUHVVRU0RGHO &RPSUHVVRU2LO &RPSUHVVRU7\SH 0,768%,6+,(/(&75,& *8$1*=+28&2035(6625 &2/7' 0,768%,6+,(/(&75,& *8$1*=+28 &2035(6625&2/7' 71%)/+0& 71%)/+0& 39()96 39()96 5RWDU\ 5RWDU\ $ &RPSUHVVRU5/$ $ &RPSUHVVRU3RZHU,QSXW : /5$ 2YHUORDG3URWHFWRU 7KURWWOLQJ0HWKRG &6& &6& (OHFWURQH[SDQVLRQYDOYH (OHFWURQH[SDQVLRQYDOYH ̚ ̚ 2SHUDWLRQWHPS & $PELHQWWHPSFRROLQJ & ̚ ̚ $PELHQWWHPSKHDWLQJ & ̚ ̚ $OXPLQXP)LQFRSSHU7XEH $OXPLQXP)LQFRSSHU7XEH ĭ &RQGHQVHU)RUP 3LSH'LDPHWHU PP ĭ 5RZV¿Q*DS PP &RLO/HQJWK/;';: PP ;; ;; USP )DQ0RWRU6SHHG 2XWGRRU 2XWSXWRI)DQ0RWRU 8QLW )DQ0RWRU5/$ )DQ0RWRU&DSDFLWRU $LU)ORZ9ROXPHRI2XWGRRU8QLW : $ ȝ) $[LDOÀRZ $[LDOÀRZ P K )DQ7\SH )DQ'LDPHWHU PP 'HIURVWLQJ0HWKRG &OLPDWH7\SH ,VRODWLRQ ĭ ĭ $XWRPDWLF'HIURVWLQJ $XWRPDWLF'HIURVWLQJ 7 7 , , ,3 ,3 0RLVWXUH3URWHFWLRQ 3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUH IRUWKH'LVFKDUJH6LGH 3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUH IRUWKH6XFWLRQ6LGH 03D 'LPHQVLRQ:;+;' PP ;; ;; 'LPHQVLRQRI&DUWRQ%R[/:+ PP ;; ;; 'LPHQVLRQRI3DFNDJH/:+ PP ;; ;; 1HW:HLJKW NJ *URVV:HLJKW NJ 03D 5HIULJHUDQW 5$ 5$ 5HIULJHUDQW&KDUJH NJ /HQJWK P *DV$GGLWLRQDO&KDUJH JP 2XWHU'LDPHWHU/LTXLG3LSH PP ĭ ĭ 2XWHU'LDPHWHU*DV3LSH PP ĭ ĭ P P &RQQHFWLRQ0D['LVWDQFH+HLJKW 3LSH 0D['LVWDQFH/HQJWK 7KHDERYHGDWDLVVXEMHFWWRFKDQJHZLWKRXWQRWLFH3OHDVHUHIHUWRWKHQDPHSODWHRIWKHXQLW &RQVWUFWLRQ9LHZV &RQVWUXFWLRQ9LHZV A16CM4H4R18 316 899 378 596 815 343 550 8QLWPP A16CM4H4R24A16CM4H4R30 892 700 341 396 946 368 560 8QLWPP 5HIULJHUDQW6\VWHP'LDJUDP 5HIULJHUDQW6\VWHP'LDJUDP outdoor indoor filter A heat exchanger A3 A1 filter B heat exchanger fan A2 outdoor heat exchanger 4-way valve B3 B1 SP filter B2 high pressure switch Note: Not available for 14K/18K model discharge silencer C heat exchanger C3 C1 filter D3 C2 D1 filter D2 gas -liquid separator Note: Not available for 14K/18K model A1:A-unit electronic expansion valve B1:B-unit electronic expansion valve C1:C-unit electronic expansion valve D1:D-unit electronic expansion valve A2:A-unit gas pipe temperature sensor B2:B-unit gas pipe temperature sensor C2:C-unit gas pipe temperature sensor D2:D-unit gas pipe temperature sensor A3:A-unit liquid pipe temperature sensor B3:B-unit liquid pipe temperature sensor C3:C-unit liquid pipe temperature sensor D3:D-unit liquid pipe temperature sensor inverter compressor D heat exchanger discharge temperature sensor 6FKHPDWLF'LDJUDP 6FKHPDWLF'LDJUDP (OHFWULFDO'DWD 0HDQLQJRIPDUNV 6\PERO &RORUV\PERO :+ :+,7( <( 5' <(*1 97 6\PERO &RORUV\PERO 6\PERO *1 *5((1 6$7 <(//2: %1 %52:1 &203 5(' %8 %/8( <(//2:*5((1 9,2/(7 %. %/$&. 2* 25$1*( 3DUWVQDPH 29(5/2$' &2035(6625 3527(&7,9(($57+ (OHFWULFDO:LULQJ A16CM4H4R18 6BN 7BU G L2 INDOOR UNIT A 5YEGN(GN) L2 INDOOR UNIT B 4BU N(1) 2BN XTB EKV EKV 5 5 WH G COMP HEATER RT2 OUTROOM TEM.SENSOR OUTTUBE TEM.SENSOR BK 5 EH 16RD 3 HEAT-C 15RD 1 FA L L7 WH FB OFAN1 LX1-1 U AP1: Main Board OG V LX1-2 W TUBE-B BU L4 YE L4 BN YE BU YEGN(GN) WARNING Please don't touch any terminal when the voltage FAN MOTOR WH BK 0 RD 0 RT4 RT5 Gas Valve Liquid Valve TEM.SENSOR TEM.SENSOR BK BK 0 RD SAT R 9BU S COMP. 10YE L4 RD X1 M of terminal P(DC+) and N(DC-) at AP1 is higher than 30V to prevent the risk of electrical shock! L7 TUBE-A C1 WH BK RD 14WH 13WH OVC-COMP L3 5 4YV 4V COM-INNER FB FA 2 3 L6 BK GY XTA YEGN(GN) T-SENSOR EXHAUST TEM.SENSOR G 2 3 G RT1 RT3 N(1) YEGN(GN) N1 AC-L N2 8YEGN(GN) 1BN 3BU BU BN BU AC-L1 N1 N1 AP2 AC-L2 N2 E(PE) 0 L1 L5 L1 L2 0 XT1 L1 L2 0 POWER 11RD C(T) 12YEGN(GN) G 0 RT6 RT7 Gas Valve Liquid Valve TEM.SENSOR TEM.SENSOR G 6FKHPDWLF'LDJUDP A16CM4H4R24 LOAD LINE INDOOR UNIT A 5BU AC-L2 N2 E(PE) 1BN BU BN L2 BU N1 N1 AC-L N2 T-SENSOR 2 YEGN(GN) G TERMINAL BLOCK INDOOR UNIT B 3 7BU ELECTRONIC EXPANSION VALVE TERMINAL BLOCK INDOOR UNIT C FB FA 3BN N(1) P 19BU COM-INNER WH XTB G 2 EKV EKV EKV 5 5 5 BK WH FA C1 YE BU FC M YEGN(GN) G FAN MOTOR W 24RD RD 0 RT8 RT9 QC YC Liquid Valve Gas Valve Tem.Sensor Tem.Sensor BK 0 COMP W COMP. 16YEGN(GN) G HEAT-C RD RD 0 RT6 RT7 QB YB Gas Valve Liquid Valve Tem.Sensor Tem.Sensor BK Overload Protector V X1 TUBE-C BK 0 YE RD V SAT U L5 13BU 14YE 15RD BU U LX2-1 TUBE-B RD 0 RT4 RT5 QA YA Gas Valve Liquid Valve TEM.Sensor Tem.Sensor BK 17WH LX2-2 LX1-1 LX1-2 AP1: Main Board WH BN BU OG WH TUBE-A CAP. RD OVC-COMP 5 FB OFAN WH BK L RD 5 5 HPS High Pressure Switch 18WH FC 3 XTC G YEGN(GN) 20YE HPP GY 2 YEGN(GN) L4 BK 2BN N(1) 4-WAY VALVE 4YV 4V 6BU EXHAUST TEM.SENSOR OUTROOM TEM.SENSOR OUTTUBE TEM.SENSOR WH 12YEGN(GN) G 3 RT2 RT3 N(1) XTA RT1 0 10BU L3 TERMINAL BLOCK BK AC-L1 AP2: N1 Filter Board 0 9YEGN(GN) POWER L1 11BN 21BN L L' 22BU NFILTER N' G L1 L2 0 XT1 L1 L2 23RD 0 Compressor Band Heater WARNING Please don't touch any terminal when the voltage of terminal P(DC+) and N(DC-) at AP1 is higher than 30V to prevent the risk of electrical shock! A16CM4H4R30 G N LOAD L1 L LINE 21BN 22BU 11BN 10BU L' N' AC-L1 N1 FILTER 9YEGN(GN) AP2 INDOOR UNIT A 5BU L2 BU BN L3 BU N1 AC-L2 N2 E(PE) N1 AC-L N2 RT1 T-SENSOR EXHAUST TEM.SENSOR OUTROOM TEM.SENSOR OUTTUBE TEM.SENSOR 0 XT1 L1 L2 0 POWER L1 L2 RT2 N(1) INDOOR UNIT B YEGN(GN) G 1BN 6BU 2 3 XTB INDOOR UNIT C 7BU 3BN N(1) 2 3 XTC YEGN(GN) INDOOR UNIT D N(1) 8BU 4BN 20YE EKV EKV EKV 5 5 5 BK FA WH BK C1 BN RD FB TUBE-A OFAN M TEM.SENSOR L BU 5 FC FD LX1-1 TUBE-B TEM.SENSOR TEM.SENSOR U LX2-1 RD BK 0 RT8 YE RD BK 0 0 RT10 RT9 Please don't touch any terminal when the voltage of terminal P(DC+) and N(DC-) at AP1 is higher than 30V to prevent the risk of electrical shock! HEAT-C W RD 15RD RD 0 24RD RT11 Liquid Valve Gas Valve TEM.SENSOR TEM.SENSOR BN:BROWN WH:WHITE BU:BLUE YE:YELLOW SAT U COMP. V X1 Gas Valve Liquid Valve TEM.SENSOR TEM.SENSOR 13BU 14YE V G WARNING L5 BU YE LX1-2 AP1: Main Board TUBE-C TUBE-D HP 18WH 17WH OVC-COMP LX2-2 WH OG 5 BK YE BU WH RD RD BK 0 0 BK 0 0 RT6 RT7 YEGN(GN) Gas Valve RT4 LiquidRT5 Liquid Valve Valve Gas Valve TEM.SENSOR FAN MOTOR YE RD 5 P 19BU FC FD 5 5 4YV 4V HPP EKV WH G L4 COM-INNER FA FB 2 3 XTD RT3 G BK GY WH RD 2BN N(1) YEGN(GN) G YEGN(GN) G 12YEGN(GN) 0 2 3 XTA W 16YEGN(GN) G 23RD COMP HEATER BK:BLACK RD:RED GY:GRAY YEGN:YELLOW GREEN 7KHVHFLUFXLWGLDJUDPVDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFHSOHDVHUHIHUWRWKHRQHVXSSOLHGZLWKWKHXQLW 6FKHPDWLF'LDJUDP 3ULQWHG&LUFXLW%RDUG A16CM4H4R18 Ɣ7239,(: 1 2 3 4 5 6 7 8 9 1 2 3 10 4 11 5 6 12 7 Outdoor fan 8 4-way valve 9 13 10 14 11 12 13 17 Ɣ%277209,(: 16 Compressor interface Unit A liquid valve and gas valve Unit B liquid valve and gas valve Compressor overload protector Temperature sensor Compressor electric heater 15 14 15 Chassis electric heater (reserved) Unit A electronic expansion valve Unit B electronic expansion valve Communication interface with indoor unit Communication neutral wire Live wire of power supply Neutral ire of power supply 16 Reactor interface1 17 Reactor interface2 6FKHPDWLF'LDJUDP A16CM4H4R24A16CM4H4R30 Ɣ7239,(: 1 2 3 4 5 6 7 8 9 10 11 12 13 1 Compressor interface 2 Temperature sensor interface of unit A liquid valve and gas valve 3 Temperature sensor interface of unit B liquid valve and gas valve 4 Temperature sensor interface of unit C liquid valve and gas valve 14 15 16 5 17 6 18 7 8 9 22 Ɣ%277209,(: 21 20 19 Temperature sensor interface of unit D liquid valve and gas valve Temperature sensor interface Interface of compressor overload protector Interface of chassis electric heater Interface of compressor electric heater belt 10 Outdoor fan interface 11 4-way valve interface 12 High voltage protection interface Interface of electronic expansion valve A Interface of electronic expansion valve B Interface of electronic expansion valve C Interface of electronic expansion valve D Communication wire interface Communication neutral wire interface 13 14 15 16 17 18 19 Input neutral wire interface 20 Input live wire interface 21 PFC input live wire interface 22 PFC input neutral wire interface )XQFWLRQDQG&RQWURO )XQFWLRQDQG&RQWURO 1 Basic functions of the system 1.1 Cooling Mode 1.1.1 Cooling conditions and process: If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling operation condition, the unit start cooling operation; in this case, the electronic expansion valve, the outdoor fan and the compressor start operation. 1.1.2 Stop in cooling operation 1.1.2.1 Compressor stops The compressor stops immediately, the outdoor fan stops after 1min. 1.1.2.2 Some of the indoor units reach the stop condition (the compressor does not stop) The compressor operates immediately according to the required frequency. For the indoor unit with no requirement, the corresponding electronic expansion valve is closed to OP. 1.1.3 Cooling mode transfers to heating mode When the unit transfers to heating mode, the 4-way valve is energized after the compressor stops for 2min. The other disposals are the same as stopping in cooling mode. 1.1.4 4-way valve: in this mode, the 4-way valve is closed. 1.1.5 Outdoor fan control in cooling mode The outdoor fan starts before 5s of the starting of compressor. The outdoor fan will run in high speed for 3min after starting and then it will run in set speed. The fan shall run at every speed for at least 80s. (When the quantity of running indoor unit is changed, the unit will enter the control described in 1.3.5.1 and 1.3.5.2); When the compressor stops, the outdoor fan runs at present speed and stops after 1min. 1.2 Dry Mode 1.2.1 The dry conditions and process are the same as those in cooling mode; 1.2.2 The status of 4-way valve: closed; 1.2.3 The temperature setting range: 16 ~ 30ć; 1.2.4 Protection function: the same as those in cooling mode; 1.2.5 In dry mode, the maximum value A of the capacity requirement percentage of single unit is 90% of that in cooling mode. The open condition of the electronic expansion valve, outdoor fan and compressor is the same as those in cooling mode. 1.3 Heating Mode 1.3.1 Cooling conditions and process: When one of the indoor units reaches the heating operation condition, the unit starts heating operation. 1.3.2 Stop in heating operation: 1.3.2.1 When all the indoor units reach the stop condition, the compressor stops and the outdoor fan stops after 1min; 1.3.2.2 Some of the indoor units reach the stop condition The compressor reduces the frequency immediately and operates according to the required frequency; 1.3.2.3 Heating mode transfers to cooling mode(dry mode), fan mode a. The compressor stops; b. the power of 4-way valve is cut off after 2min; c. the outdoor fan stops after 1min; d. the status of 4-way valve: energized; )XQFWLRQDQG&RQWURO 1.3.3 Outdoor fan control in heating mode The outdoor fan starts before 5s of the starting of compressor and then it will run in high speed for 40s; The fan shall run at every speed for at least 80s; When the compressor stops, the outdoor fan stops after 1min. 1.3.4 Defrosting function When the defrosting condition is met, the compressor stops; the electronic expansion valve of all indoor units open in big angle; the outdoor fan stops after 40s of the stop of compressor, meanwhile, the 4-way valve reverses the direction; after the 4-way valve reverses the direction, the compressor starts; then begin to calculate the time of defrosting, the frequency of the compressor rises to reach the defrosting frequency. 1.3.5 Oil-returned control in heating mode 1.3.5.1 Oil-returned condition The whole unit is operating in low frequency for a long time 1.3.5.2 Oil-returned process in heating mode The indoor unit displays “H1” 1.3.5.3 Oil-returned finished condition in heating mode The duration reaches 5min 1.4 Fan Mode The compressor, the outdoor fan and the 4-way valve are closed; temperature setting range is 16̚30ć. 2. Protection Function 2.1 Mode Conflict Protection of indoor unit When the setting mode is different of different indoor unit, the unit runs in below status: a. The mode of the first operating indoor unit is the basic mode, then compare the mode of the other indoor units to see if there is a conflict. Cooling mode (dry mode) is in conflict with heating mode. b. Fan mode is in conflict with heating mode and the heating mode is the basic mode. No matter which indoor unit operates first, the unit will run in heating mode. 2.2 Overload protection function When the tube temperature is a little low, the compressor raises the operation frequency; when the tube temperature is a little high, the compressor frequency is restricted or lows down the operation frequency; when the tube temperature is too high, the compressor protection stops running. If the discharge temperature protection continuously appears for 6 times, the compressor can’t resume running. The compressor can resume running after cutting off the power and then putting through the power. (if the running time of the compressor is longer than 7min, the protection times record will be cleared) 2.3 Discharge Protection Function When the discharge temperature is a little low, the compressor raises the operation frequency; when the discharge temperature is a little high, the compressor frequency is restricted or lows down the operation frequency; when the discharge temperature is too high, the compressor protection stops running. If the discharge temperature protection continuously appears for 6 times, the compressor can’t resume running. The compressor can resume running after cutting off the power and then putting through the power. (if the running time of the compressor is longer than 7min, the protection times record will be cleared) )XQFWLRQDQG&RQWURO 2.4 Communication malfunction Detection of the quantity of installed indoor units: After 3min of energizing, if the outdoor unit does not receive the communication data of certain indoor unit, the outdoor unit will judge that indoor unit is not installed and will treat it as it is not installed. If the outdoor unit receives the communication data of that indoor unit later, the outdoor unit will treat that unit as it is installed. 2.5 Overcurrent Protection a. Overcurrent protection of complete unit; b. phase wire current protection; c. compressor phase current protection 2.6 Compressor high-pressure protection 2.6.1 When the high-pressure switch is detected cut off for 3s continuously, the compressor will enter high-pressure protection as it stops when reaching set temperature. Meanwhile, the outdoor unit will send the signal of “high-pressure protection” to the indoor units; 2.6.2 After the appearance of high-pressure protection, when the high-pressure switch is detected closed for 6s continuously, the compressor can resume running only after cutting off the power and then putting through the power. 2.7 Compressor overload protection If the compressor overload switch is detected having movement, the indoor unit will display the corresponding malfunction as it stops when the indoor temperature reaching set temperature. When the compressor stops for more than 3min and the compressor overload switch is reset, the unit will resume operation status automatically. If the protection appears for more than 6 times (if the running time of the compressor is longer than 30min, the protection times record will be cleared), the unit can not resume operation status automatically, but can resume running only after cutting off the power and then putting through the power. 2.8 Compressor Phase-lacking Protection When the compressor starts, if one of the three phases is detected open, the compressor will enter phase-lacking protection. The malfunction will be cleared after 1min, the unit will restart and then detect if there is still has phase-lacking protection. If the phase-lacking protection is detected for 6 times continuously, the compressor will not restart but can resume running only after cutting off the power and then putting through the power. If the running time of the compressor is longer than 7min, the protection times record will be cleared. 2.9 IPM Protection 2.9.1 When the IMP module protection is detected, the unit will stop as the indoor temperature reaching set temperature, PFC is closed, display IMP protection malfunction. After the compressor stops for 3min, the unit will resume operation status automatically; if the IMP protection is detected for more than 6 times continuously (If the running time of the compressor is longer than 7min, the protection times record will be cleared), the system will stop and send the signal of module protection to indoor unit. The unit can not resume operation status automatically, but can resume running only after cutting off the power and then putting through the power. 2.9.2 IMP module overheating protection 2.9.2.1 When TIMPη85ć, prohibit to raise frequency; 2.9.2.2 When TIMP≥ 90ć, the operation frequency of compressor lows down by 15% every 90s according to the present capacity requirement of the complete unit. It will keep 90s after lowing down the frequency. After lowing down the frequency, if TIMP≥ 90ć, the unit will circulate the above movement until reaching the minimum frequency; if 85ćζTIMPζ90ć, the unit will run at this frequency; when TIMP≤ 85ć, the unit will run at the frequency according to the capacity requirement; 2.9.2.3 When TIMP≥ 95ć, the compressor stops. After the compressor stops for 3min, if TIMPζ85ć, the compressor and the outdoor fan will resume operation. ,QVWDOODWLRQ0DQXDO ,QVWDOODWLRQ0DQXDO ,QVWDOODWLRQ'LPHQVLRQ'LDJUDP A16CM4H4R18 Warning Be sure to cut off the power supply before cleaning the air conditioner; otherwise electric shock might happen. Wetting of air conditioner may cause the risk of electric shock. Make sure not to wash your air conditioner in any case. Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner. (Only use soft dry cloth moist cloth clean the air conditionercabinet). This product must not be disposed together with the domestic waste.This product has to be disposed at an authorized place for recycling of electrical and electronic appliances. The temperature of refrigerant circuit will be high,please keep the interconnection cable away from the copper tube. OUTDOOR UNIT 1 N o. Description 1 Air outlet grille 2 Valve Note:the above figures are only intended to a simple diagram of theappliance and may not correspond to the appearance of the units that have been purchased. 2 A16CM4H4R24,A16CM4H4R30 Warning If the supply cable is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. Be sure to cut off the power supply before cleaning the air conditioner;otherwise electric shock might happen. Wetting of air conditioner may cause the risk of electric shock. Make sure not to wash your air conditioner in any case. Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner. (Only use soft dry cloth moist cloth clean the air conditioner cabinet). Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary. 1 The temperature of refrigerant circuit will be high,please keep the interconnection cable away from the copper tube. OUTDOOR UNIT N o. Description 1 Air outlet grille 2 Valve Note: the above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased. 2 ,QVWDOODWLRQ0DQXDO ,QVWDOOLQJ7KH2XWGRRU8QLW Location Use bolts to secure the unit to a flat, solid floor. When mounting the unit on a wall or the roof, make sure the support is firmly secured so that it cannot move in the event of intense vibrations or a strong wind. Tighten the connections using two wrenches working in opposite directions. Caution: Installation Must be Performed in Accordance with the NEC/CEC by Authorized Personnel Only. Install the drain fitting and the drain hose (for model with heat pump only) Do not install the outdoor unit in pits or air vents Condensation is produced and flows from the outdoor unit Installing the pipes when the appliance is operating in the heating mode. In order Use suitable connecting pipes and equipment for the not to disturb neighbours and to respect the environment, refrigerant R410A. install a drain fitting and a drain hose to channel the condensate water. Install the drain fitting and rubber washer on the The refrigerant pipes must not exceed the maximum outdoor unit chassis and connect a drain hose to it as shown lengths . in the figure. Models(m) 18K 24K/30K Max.connection pipe length 20 70 Max.connection pipe length (Simple one indoor unit) 10 20 Drain-water hole Bottom frame Drain plug The refrigerant pipes must not exceed the maximum heights 5m(18K) 10m(24K/30K). Drain connecter Hose (available commercially, inner dia. 16mm) Wrap all the refrigerant pipes and joints. Humid air left inside the refrigerant circuit can cause compressor malfunction. After having connected the indoor and outdoor units, bleed the air and humidity from the refrigerant circuit using a vacuum pump. (1) Unscrew and remove the caps from the 2-way and 3way valves. (2) Unscrew and remove the cap from the service valve. (3) Connect the vacuum pump hose to the service valve. (4) Operate the vacuum pump for 10-15 minutes until an absolute vacuum of 10 mm Hg has been reached. (5) With the vacuum pump still in operation, close the low-pressure knob on the vacuum pump coupling. Stop the vacuum pump. (6) Open the 2-way valve by 1/4 turn and then close it after 10 seconds. . Check all the joints for leaks using liquid soap or an electronic leak device. (7) Turn the body of the 2-way and 3-way valves. Disconnect the vacuum pump hose. (8) Replace and tighten all the caps on the valves. Diameter (mm) Twisting moment (N.m) Φ6 15-20 Φ9.52 35-40 Φ16 60-65 Φ12 45-50 Φ19 70-75 (9) If the specification of outdoor unit gas valve is 3/8", but curstomer needs to install 1/2" indoor unit so that it is need to use a “pipe joint subassembly” (Code 06643008) to make a conversion joint with outdoor unit gas valve and connection pipe, as show in following. Vacuum pump Vacuum pump Vacuum pump (8) Secure INDOOR UNIT Refrigerant fluid direction of fiow 2-way valve 3-way valve (6) Open by 1/4 turn (7) Turn to open fully Secure inlet (2) Turn (8) Secure (7) Turn to open fully (2) Turn Valve cap Valve cap (2) Turn (8) Secure Connect to the indoor unit conversion joint ,QVWDOODWLRQ0DQXDO Use suitable instruments for the refrigerant R410A. Do not use any other refrigerant than R410A. Do not use mineral oils to clean the unit. INSTALLATION DIMENSION DIAGRAM The installation must be done by trained and qualified service personnel with reliability according to this manual. Contact service center before installation to avoid the malfunction due to unprofessional installation. When picking up and moving the units, you must be guided by trained and qualified person. Ensure that the recommended space is left around the a ppliance . A16CM4H4R18 50cm or more Space to the cover 30cm or above (Air inlet side) 30cm or above Space to the cover 50cm or above Space to the wall 200cm or above (Air outlet side) A16CM4H4R24, A16CM4H4R30 50cm or more Space to the cover 30cm or above Space to the cover 30cm or above (Air inlet side) 50cm or above Space to the wall 200cm or above (Air outlet side) This is just the schematic plan, please refer to the actual product. ,QVWDOODWLRQ0DQXDO (OHFWULFDO&RQQHFWLRQV A16CM4H4R18 1. Remove the handle at the right side plate of the outdoor unit (six screw). A16CM4H4R18 2. Remove the cable clamp, connect the connection cable and power cable with the terminal at the row of connection and fix. the connection. The fitting line distributing must be consistent with the indoor unit. terminal of line bank. Wiring should meet that of indoor unit. 3. Fix power connection wire by wire clamp. Front side plate To unit A 4. Ensure wire has been fixed well. 5. Install the handle. L1 L2 connecting cable power cable An all-pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring. Wrong wire connection may cause malfunction of some electric components.After fixing cable, ensure that leads between connection to fixed point have some space. To unit B connecting cable To the power supply L1 L2 L2 L1 The connection pipes and the connectiong wirings of the unit A and unit B must be corresponding to each other respective. The appliance shall be installed in accordance with national wiring regulations. Note: the above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased. All power cables and connection cables must be protected with conduits. ,QVWDOODWLRQ0DQXDO A16CM4H4R24 1. Remove the handle at the right side plate of the outdoor unit (ten screw). 2. Remove the cable clamp, connect the connection cable and power cable with the terminal at the row of connection and fix the connection. The fitting line distributing must be consistent with the indoor unit. terminal of line bank. To unit A Wiring should meet that of indoor unit. To unit B To unit C L1 L2 3. Fix power connection wire by wire clamp. 4. Ensure wire has been fixed well. 5. Install the handle. connection cable power cable connection cable connection cable To the power supply An all-pole disconnection switch having a contact separation of at least 3mm in all pole should be Outdoor unit L1 L2 L1 L2 connected in fixed wiring. Wrong wire connection may cause malfunction of some electric components.After fixing cable, ensure that leads between connection to fixed point have some space. Indoor unit N(1) 2 3 A The connection pipes and the connectiong wirings of the unit A ,unit B and unit C must be corresponding to each other respective. N(1) 2 3 N(1) 2 3 C B connection cable C B The appliance shall be installed in accordance with national wiring regulations. connection cable connection cable A Do not install the outdoor unit where it is exposed to the sunlight. Note:the above figure are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased. Power cable 1) The power cable should be put in from the hole under connection cable cover. 2) If connecting with two indoor units, the connection cable should be put in from hole A and hole B. 3) If connecting with three indoor units, the connection cable should be put in from hole A , B and C. 4) If connecting with four indoor units, the connection cable should be put in from hole A, B , C and D. All power cables and connection cables must be protected with conduits. ,QVWDOODWLRQ0DQXDO A16CM4H4R30 D connection cable 1. Remove the handle at the right side plate of the connection cable C outdoor unit (ten screw). 2. Remove the cable clamp, connect the connection cable and power cable with the terminal at the row of connection and fix the connection. The fitting line distributing must be consistent with the indoor unit, terminal of line bank. Wiring should meet that of indoor unit. B connection cable connection cable A 3. Fix power connection wire by wire clamp. 4. Ensure wire has been fixed well. 5. Install the handle. An all-pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring. Power cable 1) Wrong wire connection may cause malfunction of some electric components.After fixing cable, ensure that 2) leads between connection to fixed point have some space. The connect ion pipe s and the connectiong wirings of the unit A ,unit B,unit C and unit D must be corresponding to each other respective. 3) 4) The appliance shall be installed in accordance with national wiring regulations. The power cable should be put in from the hole under connection cable cover. If connecting with two indoor units, the connection cable should be put in from hole A and hole B If connecting with three indoor units, the connection cable should be put in from hole A , B and C If connecting with four indoor units, the connection cable should be put in from hole A, B , C and D. All power cables and connection cables must be protected with conduits. Do not install the outdoor unit where it is exposed to the sunlight. To unit B To unit A To unit D To unit C L1 L2 power cable connection cable connection cable connection cable connection cable To the power supply L1 L2 Outdoor unit L1 L2 Indoor unit N(1) 2 3 N(1) 2 A B 3 N(1) 2 C 3 N(1) 2 3 D HANDLING After having removed the packaging, check that the contents are intact and complete. The outdoor unit must always be kept up right. Handling must be done by suitablye quipped qualified technical personnel using equipment that is suitable for the weight of the appliance. ,QVWDOODWLRQ0DQXDO &KHFN$IWHU,QVWDOODWLRQ Check Items Problems Owing to Improper Installation Is the installation reliable? The unit may drop, vibrate or make noises Has the gas leakage been checked? May cause unsatisfactory cooling (heating) effect Is the thermal insulation of the unit May cause condensation and water dropping sufficient? Is the drainage smooth? May cause condensation and water dropping Does the power supply voltage accord The unit may bread down or the components with the rated voltage specified on the may be burned out nameplate? Are the lines and pipelines correctly The unit may bread down or the components installed? may be burned out Has the unit been safely grounded? Risk of electrical leakage. Are the models of lines in conformity The unit may bread down or the components with requirements? may be burned out Are there any obstacles near the air The unit may bread down or the components inlet and outlet of the indoor and outdoor may be burned out units? Have the length of refrigerating pipe It is not easy to decide the charge amount and refrigerant charge amount been of refrigerant. recorded? ([SORGHG9LHZVDQG3DUWVOLVW ([SORGHG9LHZVDQG3DUWV/LVW A16CM4H4R18 22 21 19 20 23 24 18 17 25 16 15 14 26 27 13 12 11 10 9 1 2 3 4 5 6 7 8 ([SORGHG9LHZVDQG3DUWVOLVW 'HVFULSWLRQ 12 3URGXFWFRGH )URQW*ULOO 4W\ &%: &DELQHW 3 &KDVVLV6XEDVV\ 3 'UDLQDJH-RLQW &RPSUHVVRU*DVNHW &RPSUHVVRUDQG¿WWLQJV 0DJQHW&RLO ZD\9DOYH$VV\ 7HPSHUDWXUH6HQVRU 7HPSHUDWXUH6HQVRU &XWRII9DOYH &XWRII9DOYH %ORFN +DQGOH$VV\ (OHFWULFH[SDQGYDOYH¿WWLQJ (OHFWULFH[SDQGYDOYH¿WWLQJ 3)&,QGXFWDQFH &ODSERDUG6XE$VV\ 7HPSHUDWXUH6HQVRU 5HDU*ULOO &RQGHQVHU$VV\ 7RS&RYHU 3 0RWRU6XSSRUW6XE$VV\ /HIW6LGH3ODWH 3 (OHFWULF%R[$VV\ )DQ0RWRU $[LDO)ORZ)DQ 7KHGDWDDERYHDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFH 3DUW&RGH A16CM4H4R18 3 ([SORGHG9LHZVDQG3DUWVOLVW A16CM4H4R24 35 34 33 32 31 30 28 29 27 26 36 25 37 38 39 24 23 22 40 21 20 19 18 17 16 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Exploded Views and Parts list Description NO. Product code 1 Front Grill 2 Cabinet 3 Drainage Plug 4 Chassis Sub-assy 5 Drainage Connecter Qty CB228W01700 01473049 1 01433047P 1 06813401 3 01203942P 1 06123401 1 6 Compressor and Fittings 00105036 1 7 Compressor Gasket 76710207 3 8 Gas-liquid Separator Assy 07225017 1 9 Inhalation Tube 03723455 1 10 Right Side Plate 0130319401P 1 11 Valve Support Assy 0710306603 1 12 Cut off Valve 07130239 1 13 Cut off Valve 07133185 1 14 big handle Assy 02113043 1 15 Terminal cover Sub-Assy 01253057 1 16 Temperature Sensor 39000073 1 17 Temperature Sensor 3900007301 1 18 Temperature Sensor 3900007302 1 19 Electric Expand Valve Fitting 4300008402 1 20 Electronic Expansion Valve assy 07133456 1 21 Electric Expand Valve Fitting 43000084 1 22 Electric Expand Valve Fitting 4300008401 1 23 Magnet Coil 4300040033 1 24 4-Way Valve Assy 03123415 1 25 Wiring clamp 26115004 1 26 PFC 电感 43120129 1 27 Clapboard Assy 01233420 1 28 Temperature Sensor 3900030901 1 29 Rear Grill 01473043 1 30 Condenser Assy 01113710 1 31 Top Cover 01255005P 1 32 Motor Support Sub-Assy 0170512001 1 33 Condenser Support Plate 01173415 1 34 Left Side Plate 01305041P 1 35 Left Handle 26235401 1 36 Electric Box (Fireproofing) 01413148 1 37 Electric Box Assy 0260370301 1 38 Tube Connector Sub-assy 39 Fan Motor 40 Axial Flow Fan The data above are subject to change without notice. 26 Part Code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⬉ᛳ &ODSERDUG$VV\ 7HPSHUDWXUH6HQVRU 5HDU*ULOO &RQGHQVHU$VV\ 7RS&RYHU 3 0RWRU6XSSRUW6XE$VV\ &RQGHQVHU6XSSRUW3ODWH /HIW6LGH3ODWH 3 /HIW+DQGOH (OHFWULF%R[)LUHSURR¿QJ (OHFWULF%R[$VV\ 7XEH&RQQHFWRU6XEDVV\ )DQ0RWRU $[LDO)ORZ)DQ 7KHGDWDDERYHDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFH 3DUW&RGH A16CM4H4R30 7URXEOHVKRRWLQJ 7URXEOHVKRRWLQJ 0DOIXQFWLRQ,QGLFDWRU Note: ○: off ●: on Ƽ: blink When several malfunctions occur at the same time, they will be displayed in circulation and every malfunction is displayed for 5s. NO 0 Malfunction description Normal stop 1 2 Compressor run Compressor overload protection 3 4 5 6 7 8 9 Discharge protection Outdoor unit overload protection High pressure protection Over current protection IMP protection IMP over heating protection PFC protection (including PFC overheating protection) 10 11 12 13 14 15 Phase current protection Over voltage protection Insufficient voltage protection Start failure Compressor desynchronizing Compressor phase-lacking protection 16 Compressor phase current detection malfunction 17 18 19 20 21 22 23 24 Memory chip mistake DC power supply circuit-short Defrosting Oil return Complete unit frequency restriction protection Complete unit frequency dropping protection Unit A frequency restriction or frequency dropping protection Unit B frequency restriction or frequency dropping protection 25 26 27 28 29 30 31 Unit C frequency restriction or frequency dropping protection Unit D frequency restriction or frequency dropping protection Outdoor ambient temperature sensor protection Outdoor tube temperature sensor protection Discharge temperature sensor protection IPM thermal resistance malfunction Unit A liquid pipe temperature sensor malfunction 32 33 34 Unit A gas pipe temperature sensor malfunction Unit B liquid pipe temperature sensor malfunction Unit B gas pipe temperature sensor malfunction 35 36 Unit C liquid pipe temperature sensor malfunction Unit C gas pipe temperature sensor malfunction 37 38 39 Unit D liquid pipe temperature sensor malfunction Unit D gas pipe temperature sensor malfunction Unit A mode conflict 40 Unit B mode conflict 41 42 Unit C mode conflict Unit D mode conflict LED1 LED2 LED3 LED4 ○ ● ○ ○ ○ ● ● ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ● ● ● ● ● ● ● ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Ƽ ○ ● Ƽ ○ ● Ƽ ○ ● Ƽ ○ ● Ƽ Ƽ Ƽ Ƽ ○ ○ ○ ● ● ● ○ ● Ƽ Ƽ Ƽ ○ ● ○ ○ ○ ● ● ● Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ ○ ○ ○ ● ● ● ○ ● Ƽ Ƽ Ƽ Ƽ ○ ● Ƽ ○ ○ ○ ● ● ● ○ Ƽ ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ● ● ● ● ● ● Ƽ ○ ● Ƽ ○ ● Ƽ ○ ● Ƽ ○ ● Ƽ ○ ● 7URXEOHVKRRWLQJ 43 Communication failure with Unit A ● Ƽ 44 45 46 47 48 49 50 51 52 Communication failure with Unit B Communication failure with Unit C Communication failure with Unit D Unit A freeze protection Unit B freeze protection Unit C freeze protection Unit D freeze protection Unit A overheating prevention protection Unit B overheating prevention protection Ƽ Ƽ ○ ● Ƽ ○ ○ ○ ● ● ● ○ ● Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ 53 54 55 56 57 58 Unit C overheating prevention protection Unit D overheating prevention protection Unit A communication wire misconnection or expansion valve malfunction Unit B communication wire misconnection or expansion valve malfunction Unit C communication wire misconnection or expansion valve malfunction Unit D communication wire misconnection or expansion valve malfunction Ƽ Ƽ Ƽ ● ● ● ● ● ● ● ● ● ● ● ○ ● ○ ○ ○ ● ● ○ ○ ○ ○ ○ Ƽ Ƽ Ƽ Ƽ Ƽ Ƽ ○ ● Ƽ ○ ● ● ● 0DOIXQFWLRQ&KHFNLQJDQG(OLPLQDWLRQ Note: discharge the position in below pictures with discharge resistance after open the top cover and check if the voltage is below 20V with universal meter, then begin to check. 18K: 24/30K: (1) IPM protection malfunction: Main checking point: ● If the input voltage of the unit is within normal range? ● If the connection wire of compressor is connected well? Is it loose? If the connection sequence is correct? ● If the resistance of compressor coil is normal? If the isolation of compressor coil with copper pipe is good? ● If the unit is overloaded? If the heat radiation of the unit is good? ● If the refrigerant charge is suitable? Flow chart: 7URXEOHVKRRWLQJ Energize the unit Please check: 1. if the indoor and outdoor heat exchanges are dirty, if there is obstacle to affect the radiation; 2. if the indoor and outdoor fans are running normally; 3. if the pressure of the system is too high; 4. if the refrigerant is too much which causes the high level of pressure; yes If the above cases are existed? no Correct according to the service manual and then energize the unit to operate no If the wire of compressor is connected well and correctly? yes Reconnect the wire of the compressor according to the correct wiring method Test the resistance between the three phases no If the resistance is normal? yes Test the isolation impedance between the three phases of the compressor and thecopper pipe yes If the resistance is above 500M ? no Replace the compressor yes Malfunction is eliminated no Replace the outdoor mainboard End 7URXEOHVKRRWLQJ (2) PFC protection malfunction Main checking points: ● If the power supply is normal; ● Check if the connection wire of induction is connected well and if the induction is broken; Flow chart: Start Check If the power supply is normal Turn on the unit after the yes power supply resumes to Power supply is abnormal normal situation no Check if the outdoor induction is broken yes The induction is broken Replace the induction no no Malfunction is eliminated Replace the outdoor mainboard yes End 7URXEOHVKRRWLQJ (3) Capacity charging malfunction Main checking points: ● If the wiring of the induction is connected well and if the induction is broken; ● If the mainboard is broken; Flow chart: Energize the unit and wait for 1min Test the voltage between the two ends of the electrolytic capacitor with the DC shift of the universal meter yes The voltage is above 100V The detection circuit of the outdoor mainboard has malfunction Replace the outdoor mainboard no Check if the induction wiring is loose or the induction is cut off The induction is cut off or the wiring is loose yes Replace the induction or reconnect the loose wire Malfunction is eliminated yes no no Replace the outdoor mainboard End 7URXEOHVKRRWLQJ (4) Anti-high temperature and overload malfunction Main checking points: ● If the outdoor ambient temperature is within the normal range; ● If the outdoor fan is running normally; ● If the indoor and outdoor radiation environment is good; Flow chart: Start yes If the outdoor ambient temperature is above 53 ć It is a normal protection, please operate the unit after the outdoor ambient temperature has changed no yes Improve the radiation environment of the unit no Check if the terminal of the fan is connected well, if the fan is broken If the indoor and outdoor radiation is insufficient no If the outdoor fan is working normally yes Replace fan capacitor Replace outdoor mainboard Replace outdoor fan End 7URXEOHVKRRWLQJ (5) Temperature sensor malfunction Main checking points: ƽ If the temperature; sensor is damaged or broken ƽIf the terminal of the temperature sensor is loosended or not connected; ƽIf the mainboard is broken; Flow chart: Start Check whether the wiring terminal between temperature sensor and controller is loosened or poorly yes contacted? Insert the temperature sensor tightly no no Check whether the temperature senspr is normal according to Eliminate the malfunction no yes Replace the temperature sensor with the same model resistance table no yes yes Eliminate the malfunction Replace the controller with the same model End 7URXEOHVKRRWLQJ (6) Start failure malfunction Main checking points: ƽ If the connection wire of the compressor is connected properly; ƽIf the stop duration of the compressor is sufficient; ƽIf the compressor is broken; ƽIf the ; refrigerant charging amount is too much; Flow chart: Energize and start the unit no If the stop duration of the compressor is longer than 3min yes If the connection wire of the compressor is connected well and correctly yes no no If the refrigerant charging amount is too much Charge the refrigerant according to the service manual yes Eliminate the malfunction no not enough, the high and low pressure of the system is not balanced, restart it after 3min Replace the outdoor mainboard yes Eliminate the malfunction no Replace the compressor End Eliminate the malfunction yes yes The stop duration of the unit is Reconnect the connection wire of the compressor according to the wiring diagram no 7URXEOHVKRRWLQJ (7) Communication malfunction Main checking points: ƽ If the connection wire between the indoor unit and outdoor unit is connected well, if the wires inside the unit is connected well; ƽIf the indoor mainboard or outdoor main board is broken; Flow chart: Communication malfunction of some indoor units De-energize,check the connection wire of indoor and outdoor unit and the wire of the eletric box is connected correctly Connected correctly no Reconnect according to the wiring diagram yes Eliminate the malfunction no yes De-energize, change the communication wire of the wellcommunicated indoor unit and malfunction indoor unit, then energize the unit and wait for 3min The malfunction indoor unit resumes normal yes Replace outdoor mainboard no Replace the mainboard of the malfunction indoor unit End 7URXEOHVKRRWLQJ All the indoor units appear communication malfunction De-energize,check the connection wire of indoor and outdoor unit and the wire of the eletric box is connected correctly no Reconnect according to Connected correctly? yes Eliminate the malfunction the wiring diagram yes De-energize, check if the connection wire between the outdoor mainboard and the filter board according to the wiring diagram Reconnect according to the wiring diagram no Connected correctly? yes Eliminate the malfunction no yes yes The connection wire is broken? Replace the connection wire yes Eliminate the malfunction no no Check if there is power input bewtween the netrual wire and live wire of the outdoor mainboard no There is power input? Replace the filter board of the outdoor unit no yes Replace the outdoor mainboard Resume communication? yes End yes Eliminate the malfunction no Replace indoor mainboard 7URXEOHVKRRWLQJ (8) Compressor overload, diacharge protection malfunction Main checking points: ƽ If the eletric expansion valve is connected well or it is broken; ƽIf there is refrigerant leakage; ƽIf the overload protector is broken; Flow chart: Start If the overload protector is connected well? no yes no Check the resistance between the two ends of the overload protector in ambient temperature, if the resistance is below 1k yes If the wiring of the eletric expansion valve is coonected well? Replace the overload protector no Reconnect according to the wiring diagram Check the coil of the eletric expansion valve, replace it if it is broken Eliminate the malfunction yes no Check the refrigerant status, if there is refrigerant leakage, recharge it according to the service manual yes Eliminate the malfunction no Replace outdoor mainboard End Noted: the detection method of the coil of the eletric expansion valve: there is five pieces of the coil of the eletric expansion valve, the resistance of one of them (the leftmost or the rightmost one) is almost the same as the resistance of other terminal (within 100 ). Judge the condition of the electronic expansion valve through detecting these resistance. 7URXEOHVKRRWLQJ (9) Compressor desynchronizing malfunction Main checking points: ƽ If the pressure of the system is too high; ƽIf the eletric expansion valve is working normally or it is broken; ƽIf the radiation of the unit is good; Flow chart: The unit appears desynchronizing as soon as energizing and starting no The stop duration of the compressor is longer than 3min? yes The wiring of the compressor is no Reconnect the wire properly connected properly? yes no yes Eliminate the malfunction no Replace the eletric expansion valve The eletric expansion valve is broken? yes no yes Eliminate the malfunction Replace outdoor mainboard yes Eliminate the malfunction no Replace the compressor End 7URXEOHVKRRWLQJ $SSHQGL[5HVLVWDQFH7DEOHRI$PELHQW7HPSHUDWXUH6HQVRUIRU,QGRRUDQG2XWGRRU8QLWV. 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7URXEOHVKRRWLQJ $SSHQGL[5HVLVWDQFH7DEOHRI2XWGRRUDQG,QGRRU7XEH7HPSHUDWXUH6HQVRUV. 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7URXEOHVKRRWLQJ $SSHQGL[5HVLVWDQFH7DEOHIRU2XWGRRU'LVFKDUJH7HPSHUDWXUH6HQVRU. 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 7HPSć 5HVLVWDQFHNȍ 1RWH7KHLQIRUPDWLRQDERYHLVIRUUHIHUHQFHRQO\ 5HPRYDO3URFHGXUH 5HPRYDO3URFHGXUH 5HPRYDO3URFHGXUH. :DUQLQJ%HVXUHWRZDLWIRUDPLQLPXPRIPLQXWHVDIWHU WXUQLQJRIIDOOSRZHUVXSSOLHVEHIRUHGLVDVVHPEO\ 3URFHGXUH 6WHSV 5HPRYHWRSFRYHUDQGKDQGOH %HIRUHGLVDVVHPEO\ 7ZLVWRIIWKHVFUHZVXVHGIRU¿[LQJWKHKDQGOHSXOO WKHKDQGOHXSZDUGWRUHPRYHLW +DQGOH 7RSSDQHO 7ZLVW RII WKH VFUHZV XVHG IRU ¿[LQJ WKH WRS FRYHU SXOOWKHWRSFRYHUXSZDUGWRUHPRYHLW 5HPRYDO3URFHGXUH 3URFHGXUH 6WHSV 5HPRYHIURQWJULOOHDQGIURQWSDQHO 5HPRYH WKH VFUHZV FRQQHFWLQJ WKH IURQW JULOOH DQGWKHIURQWSDQHO5HPRYHWKHIURQWJULOOH )URQWJULOOH 7ZLVW RII WKH VFUHZV IL[LQJ WKH SDQHO SXOO LW XSZDUGORRVHQWKHFODVSRQWKHULJKWVLGHURWDWH LWWRWKHOHIWDQGWKHQUHPRYHWKHIURQWSDQHO )URQWSDQHO 5HPRYHULJKWVLGHSODWH 5HPRYH WKH VFUHZV FRQQHFWLQJ WKH ULJKW VLGH SODWHZLWKWKHFKDVVLVWKHYDOYHVXSSRUWDQGWKH HOHFWULFER[DQGWKHQUHPRYHWKHULJKWVLGHSODWH DVV\ ULJKWVLGH SODWH 5HPRYHWKHVFUHZVFRQQHFWLQJWKHOHIWVLGHSOD WHDQGWKHFKDVVLVDQGWKHQUHPRYHWKHOHIWVLGH SODWHDVV\ /HIW6LGH3ODWH 5HPRYDO3URFHGXUH 3URFHGXUH 6WHSV 5HPRYHWKHD[LDOÀRZIDQ 5HPRYH WKH QXWV ¿[LQJ WKH EODGH DQG WKHQUHPRYH WKHD[LDOÀRZIDQ $[LDO)ORZ)DQ 5HPRYHWKHWDSSLQJVFUHZV¿[LQJWKHPRWRUGLV FRQQHFWWKHOHDGLQJZLUHLQVHUWRIWKHPRWRUDQGWKHQ UHPRYHWKHPRWRU5HPRYHWKHWDSSLQJVFUHZV ¿[LQJWKHPRWRUVXSSRUWDQGWKHQSXOOWKHPRWRUVXS SRUWXSZDUGVWRUHPRYHLW IDQPRWRU ¿[LQJIUDPH IDQPRWRU 5HPRYH(OHFWULF%R[$VV\ 5HPRYHWKHVFUHZV¿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¿[LQJYDOYHVXSSRUWDQGFKDVVLV DQGWKHQUHPRYHWKHYDOYHVXSSRUWVXEDVV\ YDOYHVXSSRUW VXEDVV\ 5HPRYHLVRODWLRQVKHHW 5HPRYH VFUHZV IL[LQJ LVRODWLRQ VKHHW DQG WKHQ UHPRYHWKHLVRODWLRQVKHHW LVRODWLRQVKHHW